Bus communication

Application

AS 235, AS 235 H and AS 235 K can only be operated on the CS 275 plant bus, but can also communicate with automa- tion systems and operator systems on the PROFIBUS-TM plant bus via a CS-L2 bridge.

This section only describes bus communication with the CS 275 plant bus. A description of bus communication via the PROFIBUS-TMplant bus can be found in Catalog PLT 112.

When planning TELEPERM M systems with the CS 275 plant bus, please observe the TELEPERM M design guidelines in the manual "Information and guidelines for planning, instal- lation and operation", C79000-G8000-C417 (German) or C79000-G8076-C417 (English).

Application

￿The AS 235, AS 235 H and AS 235 K automation systems are connected together and to other automation systems and oper- ator systems of the TELEPERM M process control system via the CS 275 bus in medium-sized and large plants.

Central process control is carried out using the OS 525 and WinCC/TM-OS operator systems. SIMATIC PC or other AT-com- patible personal computers, PG programming devices and computers from other manufacturers can be connected to the bus system for higher-level tasks.

Sequential transfer of data between the individual participants is in time-division multiplex mode. Participants within a local area or a cabinet group are connected over distances of up to 20 m by a local bus. A remote bus connects distributed systems over distances of up to 4 km.

A redundant design of the bus line increases of the availability of the CS 275 plant bus. The remote bus network can be extended to a maximum length of 3 x 4 km using bus couplers.

￿

Design

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The CS 275 bus system consists of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• a local bus which is always redundant and

 

 

 

 

 

 

 

 

 

 

• a remote bus which can be either of single or redundant

 

design.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OS 525

-AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WinCC/TM-OS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote bus,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

max. 4 km

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Redundant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UI

 

 

 

 

local bus,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

max. 20 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AS

-AS

 

AS

-AS

 

AS

-AS

 

AS

-AS

 

-AS

 

AS

-AS

 

 

 

235/K

 

235/K

 

235/K

 

235/K

 

 

235H

 

 

 

N

 

N

 

N

 

N

 

N

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6/1 CS 275 bus system; example of connection of local bus and remote bus, single remote bus

 

 

 

 

 

 

 

OS 525

-AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WinCC/TM-OS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UI

 

UI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Redundant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote bus,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

max. 4 km

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Redundant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UI

 

UI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UI

 

UI

 

 

 

 

local bus,

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

max. 20 m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AS

-AS

 

 

 

AS

-AS

 

 

 

 

AS

-AS

 

 

AS

-AS

 

-AS

 

AS

-AS

 

235/K

 

 

235/K

 

235/K

 

 

235/K

 

 

235H

 

N

 

 

 

N

 

 

 

 

N

 

 

N

 

N

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6/2 CS 275 plant bus; example of connection of local bus and remote bus, redundant remote bus

Local range

4 line signals are used in the local range. The data are transmit- ted sequentially on one data line. A second line transmits the clock, the third is used for synchronization. The fourth line is required to switch over data transmission to channel A or B of the redundant local bus. The wired-OR technique is used with the local bus for coupling.

The interface modules for the local bus have a redundant local bus interface. They are connected together with one cable in which the local bus is redundant.

The max. length of the local bus cable is 20 m.

Front plug

 

 

N-AS

 

 

N-AS

 

N-AS

 

 

6DS8 201-8..

S max. 20 m

 

 

 

 

 

 

 

 

6DS8 204-8../

Max. 9 CS 275 modules

 

 

 

 

 

 

 

6DS8 205-8../

 

 

 

 

 

 

6DS9 201-8CA

 

 

 

 

 

Fig. 6/3 Local bus coupling between AS 235 and AS 235 K

 

 

 

AS 235 H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front

 

 

N-AS

 

 

N-AS

 

N-AS

 

 

 

 

 

 

 

 

plug

 

 

 

 

 

 

 

 

 

 

 

 

6DS8 201-8..

S max. 20 m

 

 

 

6DS8 204-8../

Max. 9 CS 275 modules

 

6DS9 201-8CA

 

 

 

 

 

 

Fig. 6/4 Local bus coupling with AS 235 H

6/2

Siemens PLT 111 · 1999

Image 73
Contents Teleperm M Brief description IntroductionFunctions of the AS 235 system ConfiguringGeneral system data System dataTechnical data of automation systems Or user-configured with own System architecture ConfiguringPerformance characteristics Operation and monitoring TML languageScope of performance Redundancy with the AS 235 H automation system Redundancy with AS 235 HImportant note Standard function blocks ConfiguringStandard function blocks Blocks for analog and digital processingData blocks Blocks for signal exchange via CSType Designation Function For modules with Order No Driver blocks for I/O modulesDriver blocks for I/O modules with standardized display Driver blocks for configurable Teleperm ME I/O modulesOrganization blocks Output blocks for printer and process monitorSystem architecture Performance characteristics Summary of system properties Redundancy with AS 235 H Configuring Data blocks Driver blocks for I/O modules Driver blocks for configurable Teleperm ME I/O modules Output blocks for printer and process monitor AS 235 H Connection diagramsAS 235 K ES 100 KGeneral GeneralAS 235 automation system Basic cabinetBasic cabinet Basic unitExtension units Standard I/O devicesBus components Power supply componentsOrdering data Ordering data for basic cabinetAS 235 automation system Basic cabinetOptions for AS 235 basic Cabinet Options for basic cabinet6DS9 002-8BB See page 6/6Extension cabinet Extension cabinetExtension cabinet Options for AS 235 extension CabinetAS 235 H automation system AS 235 HAS 235 H automation system, design 6DS3 305-8BA Example of redundancy with Redundant process I/OsInterface modules for 20-m local bus N-AS AS 235 H automation system Options for AS 235 H basic Cabinet AS 235 H extension cabinet AS 235 H automation Ordering data for extension cabinetSystem Extension cabinet Options for AS 235 H exten Sion cabinetBasic system AS 235 KAS 235 K automation system Basic systemAS 235 K automation system, design Interface module for ES 100 KOrdering data for AS 235 K HousingAS 235 K automation SystemES 100 K extension system ES 100 KES 100 K extension system ES 100 K extension Ordering data for ES 100 KES 100 K options Standard cabinets and accessories Standard cabinets and accessoriesSystem cabinet accessories Standard cabinetsOrdering data for system cabinet accessories Permissible thermal loading Configuring values for thermal loadStandard cabinet with heat exchanger Standard cabinets IP 20 without heat exchanger Technical dataDesign 12 Standard cabinet with heat exchanger Standard cabinets IP 54 with heat exchangerProcess connection systems Connections for process signal cablesProcess connection systems Process connection systemsConnection diagrams for standard I/O devices to AS AS 235 K Connection diagramsStandard I/O devices to AS 235 / AS 235 K Connection of personal computer Connection of personal computerConnection of process monitors and parallel monitors Connection of process monitors and parallel monitorsStandard I/O devices to AS 235 H Connection diagrams for standard I/O devices to AS 235 HConnection diagrams Connecting cable Plug Cable Max. cable Order No From Length Summary of connecting cablesFunction modules Signal modulesProportioning Counter modules Summary Configurable I/O modules General technical dataLightning protection with distributed configuration Power supply, earthingModules from other systems Selection criteria for I/O modulesClosed-loop control modules Function modulesFunction modules Closed-loop control modulesSignal modules Signal modulesAnalog input and output modules Binary input and output modules Binary input and output modulesBinary input module, testable, 6DS1 618-8CA Binary output module with 16 relays, 6DS1 605-8BAProportioning and counter modules STRUK-AS 220 EA configuring programProportioning counter module, metering pulse input module Metering pulse input module with 8 channels, 6DS1 607-8ABModules which can be used on the I/O bus Modules which can be used on the I/O busExplanations for the column Release Explanations for the column Remarks6DS1 342-1BD With S5KE Test mode Mode of operationOperation unit PBT 65 process operation keyboardConfiguring keyboard Configuring unitConfiguring keyboard Mini floppy disk unit Mini floppy disk unitMini floppy disk unit 6DS3 900-8AE Floppy disksBus communication Application ApplicationLocal range Remote range DesignSingle remote bus Connection distributor AV Connector board AF Remote busBus converter Ul Redundant remote busBus configurations, examples Bus configurationsApplication Other conditions Connecting cables Connecting cables for 20-m local bus Connecting cablesConnecting cables for remote bus Central controllers Expansion unitsSimatic S5 I/Os ET 100U Coupling of other systems Interface modules for coupling with other systems, summaryParallel coupling with S5-115U I/O modules Simatic S5 expansion unitsParallel coupling with Simatic S5-115U I/O modules Digital input modules Simatic S5-115U I/O modules appropriate for couplingDigital output modules Digital input/output modulesParallel coupling with Simatic S5-135U/155U I/O modules Parallel coupling with S5-135U/155U I/O modulesSimatic S5-135U/155U I/O modules appropriate for coupling Interface module for Simatic S5 expansion units Interface module for Simatic S5 expansion unitsSerial coupling With Simatic S5/S7 central controllers Simatic S5/S7 central controllersSerial coupling with Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllersSerial coupling with Simatic S5 I/Os Simatic S5 I/Os / ET 100UExi modules ET 100U I/O modules appropriate for couplingInterface module for ET 100U Interface module for ET 100UOrdering information Ordering of complete systems AS 235 standard configurationOrdering of options