Siemens AS 235 appendix Summary of connecting cables

Page 58

This catalog is out of date, see note on page 1

Automation systems

Connection diagrams

Summary of connecting cables

Item

Connecting cable

 

Plug 1

Plug 2

Cable

Max. cable

Order No.

Page

 

From

To

 

 

 

length

 

 

102

Configuring key-

Signal distribution unit

15-contact

15-contact

L-YCY

10 m 2)

6DS8 102-8..

5/8

 

board

6DS9 913-8DA 1)

(Cannon, sockets)

(Cannon, pins)

12 x 2 x 0.22

 

 

 

 

 

or process operation

 

 

 

 

 

 

 

 

keyboard

 

 

 

 

 

 

103

Process operation

Power supply module

9-contact

S400-A002-E

H03YY-F30

10 m

6DS8 103-8..

5/5

 

keyboard

SV 1 or

(Cannon, sockets)

(Fischer, WW)

0.75 gr

 

 

 

 

 

power supply subrack

 

 

 

 

 

 

104

Process operation

External power supply

9-contact

Without plug

H03YY-F30

10 m

6DS8 104-8..

5/5

 

keyboard

DC 24 V

(Cannon, sockets)

 

0.75 gr

 

 

 

116

Process monitor

Interface module for

Coaxial plug

BNC plug

2YCYCY

80 m

6DS8 116-8..

5/4

 

 

operation channel

 

 

1 x 0.6/3.7-75

 

 

 

 

 

6DS1 330-8CA

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

video relay (AS 235 H)

 

 

 

 

 

 

117

Process monitor

Process monitor

BNC plug

BNC plug

2YCYCY

300 m 3)

6DS8 117-8..

5/4

 

 

 

 

 

1 x 0.6/3.7-75

 

 

 

167-

Printer

Interface module for

25-contact

9-contact

LiYCY

100 m

6XV2 167-8A.

5/7

8A

 

operation channel

(Cannon, pins)

(Cannon, pins)

2 x 2 x 0.5

 

 

 

 

 

6DS1 330-8CA

 

 

 

 

 

 

 

 

(AS 235/AS 235 K)

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

printer distributor for

 

 

 

 

 

 

 

 

operation channel 1 or

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

(AS 235 H)

 

 

 

 

 

 

167-

Configuring key-

Interface module for

15-contact

15-contact

LiYCY

10 m

6XV2 167-8B.

5/8

8B

board

operation channel

(Cannon, sockets)

(Cannon, pins)

8 x 0.25

 

 

 

 

 

6DS1 330-8CA

 

 

 

 

 

 

 

 

(AS 235/AS 235 K)

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

keyboard distributor

 

 

 

 

 

 

 

 

for operation channel 1

 

 

 

 

 

 

 

 

or 2

 

 

 

 

 

 

 

 

(AS 235 H)

 

 

 

 

 

 

167-

Process operation

Interface module for

15-contact

15-contact

LiYCY

150 m 2)

6XV2 167-8C.

5/5

8C

keyboard

operation channel

(Cannon, sockets)

(Cannon, pins)

2 x 2 x 0.5

 

 

 

 

 

6DS1 330-8CA

 

 

 

 

 

 

 

or

(AS 235/AS 235 K)

 

 

 

 

 

 

 

signal distribution

or

 

 

 

 

 

 

 

keyboard distributor

 

 

 

 

 

 

 

unit

for operation channel 1

 

 

 

 

 

 

 

6DS9 913-8DA 1)

or 2

 

 

 

 

 

 

 

 

(AS 235 H)

 

 

 

 

 

 

174

Interface module

Programming device

15-contact

25-contact

LiYCY

10 m

6DS8 174-8AD

2/10

 

for operation chan-

or personal computer

(Cannon, pins)

(Cannon, pins)

5 x 0.14 gr

 

 

 

 

nel

 

 

 

 

 

 

 

 

or

 

 

 

 

 

 

 

 

signal distribution

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

6DS9 913-8DA 1)

 

 

 

 

 

 

 

201

Interface module

Interface module for

ES 902 plug

End of cable pre-

LiYCY

0.3 to 15 m

6DS8 201-8..

6/6

 

for 20-m local bus,

20-m local bus,

 

pared for plug con-

12 x 2 x 0.22

(over n par-

 

 

 

n-thparticipant

(n-1)thparticipant

 

nection

VZNSi

ticipants

 

 

 

 

(n 9)

 

 

 

20 m)

 

 

204

Interface module

Bus converters UI1

ES 902 plug

ES 902 plug (also

LiYCY

0.3 m

6DS8 204-8..

6/6

 

for 20-m local bus

and UI2

 

3rd plug)

12 x 2 x 0.22

(UI1-UI2)

 

 

 

 

 

 

 

VZNSi

0.3 to 5 m (UI

 

 

 

 

 

 

 

 

interface

 

 

 

 

 

 

 

 

module)

 

 

205

Interface module

Bus converter UI

ES 902 plug

ES 902 plug

LiYCY

0.3 to 5 m

6DS8 205-8..

6/6

 

for 20-m local bus

 

 

 

12 x 2 x 0.22

 

 

 

 

 

 

 

 

VZNSi

 

 

 

 

 

 

 

 

 

 

 

 

1)The signal distribution unit is no longer available.

2)Always applicable: length of connecting cables 167-8C + 102 max. 150 m

3)In the case of parallel monitors, max. total cable length from the RGB signal source (interface module for operation channel) up to last process monitor ￿

3/34

Siemens PLT 111 · 1999

Image 58
Contents Teleperm M Introduction Brief descriptionConfiguring Functions of the AS 235 systemSystem data General system dataTechnical data of automation systems Or user-configured with own Configuring System architecturePerformance characteristics Operation and monitoring TML languageScope of performance Redundancy with the AS 235 H automation system Redundancy with AS 235 HImportant note Standard function blocks ConfiguringStandard function blocks Blocks for analog and digital processingBlocks for signal exchange via CS Data blocksDriver blocks for I/O modules Type Designation Function For modules with Order NoDriver blocks for configurable Teleperm ME I/O modules Driver blocks for I/O modules with standardized displayOutput blocks for printer and process monitor Organization blocksSystem architecture Performance characteristics Summary of system properties Redundancy with AS 235 H Configuring Data blocks Driver blocks for I/O modules Driver blocks for configurable Teleperm ME I/O modules Output blocks for printer and process monitor AS 235 K Connection diagramsAS 235 H ES 100 KGeneral GeneralBasic cabinet Basic cabinetAS 235 automation system Basic unitStandard I/O devices Extension unitsPower supply components Bus componentsAS 235 automation system Ordering data for basic cabinetOrdering data Basic cabinet6DS9 002-8BB Options for basic cabinetOptions for AS 235 basic Cabinet See page 6/6Extension cabinet Extension cabinetExtension cabinet Options for AS 235 extension CabinetAS 235 H AS 235 H automation systemAS 235 H automation system, design 6DS3 305-8BA Redundant process I/Os Example of redundancy withInterface modules for 20-m local bus N-AS AS 235 H automation system Options for AS 235 H basic Cabinet AS 235 H extension cabinet System Extension cabinet Ordering data for extension cabinetAS 235 H automation Options for AS 235 H exten Sion cabinetAS 235 K automation system AS 235 KBasic system Basic systemInterface module for ES 100 K AS 235 K automation system, designAS 235 K automation HousingOrdering data for AS 235 K SystemES 100 K extension system ES 100 KES 100 K extension system ES 100 K extension Ordering data for ES 100 KES 100 K options System cabinet accessories Standard cabinets and accessoriesStandard cabinets and accessories Standard cabinetsOrdering data for system cabinet accessories Permissible thermal loading Configuring values for thermal loadStandard cabinet with heat exchanger Standard cabinets IP 20 without heat exchanger Technical dataDesign Standard cabinets IP 54 with heat exchanger 12 Standard cabinet with heat exchangerProcess connection systems Connections for process signal cablesProcess connection systems Process connection systemsConnection diagrams for standard I/O devices to AS AS 235 K Connection diagramsStandard I/O devices to AS 235 / AS 235 K Connection of personal computer Connection of personal computerConnection of process monitors and parallel monitors Connection of process monitors and parallel monitorsConnection diagrams for standard I/O devices to AS 235 H Standard I/O devices to AS 235 HConnection diagrams Summary of connecting cables Connecting cable Plug Cable Max. cable Order No From LengthFunction modules Signal modulesProportioning Counter modules Summary General technical data Configurable I/O modulesModules from other systems Power supply, earthingLightning protection with distributed configuration Selection criteria for I/O modulesFunction modules Function modulesClosed-loop control modules Closed-loop control modulesSignal modules Signal modulesAnalog input and output modules Binary input module, testable, 6DS1 618-8CA Binary input and output modulesBinary input and output modules Binary output module with 16 relays, 6DS1 605-8BAProportioning counter module, metering pulse input module STRUK-AS 220 EA configuring programProportioning and counter modules Metering pulse input module with 8 channels, 6DS1 607-8ABModules which can be used on the I/O bus Modules which can be used on the I/O busExplanations for the column Release Explanations for the column Remarks6DS1 342-1BD With S5KE Operation unit Mode of operationTest mode PBT 65 process operation keyboardConfiguring keyboard Configuring unitConfiguring keyboard Mini floppy disk unit 6DS3 900-8AE Mini floppy disk unitMini floppy disk unit Floppy disksBus communication Application ApplicationLocal range Remote range DesignSingle remote bus Bus converter Ul Connector board AF Remote busConnection distributor AV Redundant remote busBus configurations, examples Bus configurationsApplication Other conditions Connecting cables Connecting cables for 20-m local bus Connecting cablesConnecting cables for remote bus Central controllers Expansion unitsSimatic S5 I/Os ET 100U Interface modules for coupling with other systems, summary Coupling of other systemsParallel coupling with S5-115U I/O modules Simatic S5 expansion unitsParallel coupling with Simatic S5-115U I/O modules Digital output modules Simatic S5-115U I/O modules appropriate for couplingDigital input modules Digital input/output modulesParallel coupling with S5-135U/155U I/O modules Parallel coupling with Simatic S5-135U/155U I/O modulesSimatic S5-135U/155U I/O modules appropriate for coupling Interface module for Simatic S5 expansion units Interface module for Simatic S5 expansion unitsSerial coupling With Simatic S5/S7 central controllers Simatic S5/S7 central controllersSerial coupling with Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllers Interface module for Simatic S5/S7 central controllersSimatic S5 I/Os / ET 100U Serial coupling with Simatic S5 I/OsET 100U I/O modules appropriate for coupling Exi modulesInterface module for ET 100U Interface module for ET 100UOrdering information Ordering of complete systems AS 235 standard configurationOrdering of options