DeviceNet Network Scanner DVPDNET-SL
Status | Explanation |
0 | No explicit message is sent out. |
|
|
1 | The communication of explicit message is successful. |
|
|
2 | The explicit message is being sent out. |
3 | Error: No response from the target equipment. |
|
|
4 | Error: Command is invalid. |
|
|
5 | Error: Size of request message is invalid. |
|
|
6 | Error: Size of reponse message is invalid. |
|
|
7 | Error: Failing to establish a connection to the target equipment. |
8 ~ 255 | Reserved |
|
|
3.Notes:
Before sending explicit message by using WPL program, we suggest you clear the request message editing area and response message editing area to 0.
If the slava responds with standard error code, and
4.Application example (I)
Target
When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502
(1) The connection
DVP DNETDV P28SV
RU N
STOP
Node Address:00
DeviceNet
Node Address:02
RJ12
(2)Compulsory settings and explanations on devices Compulsory settings in
Parameter | Set value | Explanation | |
Node address | 00 | Set the node address of | |
|
|
| |
Baud rate | 500kbps | Set the communication speed of | |
“500kbps”. | |||
|
|