Delta Electronics DVPDNET-SL manual H0101 D6250 ReqID = 01, Command =

Page 25

DeviceNet Network Scanner DVPDNET-SL

„ Compulsory settings in IFD9502

 

Parameter

Set value

Explanation

 

Node address

02

Set the node address of IFD9502 to “02".

 

 

 

 

 

Baud rate

500kbps

Set the communication speed of IFD9502 and bus to

 

“500kbps”.

 

 

 

„ Compulsory settings in VFD-B

 

 

 

 

 

 

Parameter

Set value

Explanation

 

02-00

04

The main frequency is operated on RS-485 interface.

 

 

 

 

 

02-01

03

The operation commands are operated on the communication

 

interface. Operation by keys is valid.

 

 

 

 

09-00

01

Communication address of VFD-B: 01

 

 

 

 

 

09-01

03

Baud rate: 38,400

 

 

 

 

 

09-04

03

Modbus RTU mode. Data format <8, N, 2>

 

 

 

 

„Explanations on devices

PLC device

Content

 

 

 

 

 

 

Explanation

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

 

 

 

 

D6250

0101Hex

 

 

ReqID = 01Hex

 

Command = 01Hex

 

 

 

 

 

 

 

 

 

 

D6251

0005Hex

 

 

Port = 00Hex

 

 

Size = 05Hex

 

 

 

 

 

 

 

Request

D6252

0E02Hex

 

Service Code = 0EHex

 

MAC ID = 02Hex

message

D6253

0001Hex

High bye of Class ID =00Hex

Low byte of Class ID = 01Hex

editing area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6254

0001Hex

High byte of Instance ID =

Low byte of Instance ID =

 

 

 

 

 

00Hex

 

 

 

01Hex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6255

0001Hex

 

 

 

N/A

 

Attribute ID = 01Hex

 

 

 

 

 

 

 

 

 

 

D6000

0101Hex

 

 

ReqID = 01Hex

 

 

Status = 01Hex

Response

D6001

0002Hex

 

 

Port = 00Hex

 

 

Size = 02Hex

message

D6002

8E02Hex

 

Service Code = 8EHex

 

MAC ID = 02Hex

editing area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D6003

031FHex

High byte of Service Data =

Low byte of Service Data =

 

 

 

 

 

03Hex

 

 

 

1FHex

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) PLC program

M1002

ZRST D6000 D6031

ZRST D6250 D6281

M0

Reset response message editing area & request message editing area

MOV

H0101

D6250

ReqID = 01, Command = 01

MOV

H0005

D6251 Port = 00, Size = 05

MOV

H0E02

D6252

Service Code = 0E, MAC ID = 02

MOV

H0100

D6253

Class ID to be read = 01

MOV

H0100

D6254

Instance ID to be read = 01

MOV

H0100

D6255

Attribute ID to be read = 01

DVP-PLC Application Manual

23

Image 25
Contents DVPDNET-SL Page Table of Contents Principle of Bit-Strobe Digital Indicator LEDDisplay of Node Status in Scan List Status of DVPDNET-SL Introduction FeaturesCan I/O Scan ListProduct Profile & Outline DimensionVDC Canl DVPDNET-SL PINShield CanhBasic Operation Installing DVPDNET-SL and DVP-SV MPU on DIN RailIN1 Corresponding Relation between DVPDNET-SL and DVP-SV ConfigurationConstructing DeviceNet Network How to Construct a DeviceNet NetworkI/O Mapping Table RTU-DNET DVP-SV COM1Ascii DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DVPDNET-SL Slave → DVPDNET-SL Register Devices in slave PLC program Principle of Explicit Message Sending Sending Explicit Message from Ladder DiagramMAC ID Node Address00 DeviceNet Node Address02 H0101 D6250 ReqID = 01, Command = DeviceNet Network Scanner DVPDNET-SL H0008 D6251 Port = 00, Size = Display of Node Status on Network Bit-Strobe CommandDisplay of Node Status in Scan List PLCPower LED LED Indicator & Trouble-shootingNS LED MS LED MS LEDCorrection is needed Memo