Delta Electronics DVPDNET-SL manual Constructing DeviceNet Network, I/O Mapping Table

Page 11

DeviceNet Network Scanner DVPDNET-SL

DVPDNET-SL

Mapped D registers

index

Output mapping

Input mapping

1

D6250 ~ D6497

D6000 ~ D6247

 

 

 

2

D6750 ~ D6997

D6500 ~ D6747

3

D7250 ~ D7497

D7000 ~ D7247

 

 

 

4

D7750 ~ D7997

D7500 ~ D7747

 

 

 

5

D8250 ~ D8497

D8000 ~ D8247

 

 

 

6

D8750 ~ D8997

D8500 ~ D8747

 

 

 

7

D9250 ~ D9497

D9000 ~ D9247

8

D9750 ~ D9997

D9500 ~ D9747

 

 

 

4.2I/O Mapping Table

 

Output mapping are

 

 

Input mapping area

 

D register

Mapping area

Data length

D register

Mapping area

Data length

D6250 ~ D6281

Explicit message

32 words

D6000 ~ D6031

Explicit message

32 words

program request

program response

D6282 ~ D6285

Bit-strobe command

4 words

D6032 ~ D6035

Status of nodes in the

4 words

scan list

D6286

Reserved

1word

D6036

DVPDNET-SL status

1 word

D6287 ~ D6476

DeviceNet output data

190 words

D6037 ~ D6226

DeviceNet input data

190 words

 

 

 

 

 

 

D6477 ~ D6497

Reserved

21 words

D6227 ~ D6247

Reserved

21 words

5 Constructing DeviceNet Network

In this section, we will present an application example, illustrating how to construct a DeviceNet network and the configuration of the network. Before constructing a network, you have to first know clearly what the network is for and start a preliminary planning for the data to be exchanged. The plan shall include the maximum communication distance, slaves to be used, total length of data to be exchanged and so on. These information will decide whether the network you construct is a reasonable one, or if it satisfies your needs, and even affect the later-on network sustainability and flexibility of network capacity upgrade.

5.1How to Construct a DeviceNet Network

Target

Using a remote digital I/O module to control RUN/STOP of VFD-B AC motor drive.

1. The connection

DVP-PLC Application Manual

9

Image 11
Contents DVPDNET-SL Page Table of Contents Display of Node Status in Scan List Status of DVPDNET-SL Digital Indicator LEDPrinciple of Bit-Strobe Introduction FeaturesCan I/O Scan ListProduct Profile & Outline DimensionCanh DVPDNET-SL PINVDC Canl ShieldIN1 Installing DVPDNET-SL and DVP-SV MPU on DIN RailBasic Operation Corresponding Relation between DVPDNET-SL and DVP-SV ConfigurationI/O Mapping Table How to Construct a DeviceNet NetworkConstructing DeviceNet Network RTU-DNET Ascii COM1DVP-SV DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DVPDNET-SL Slave → DVPDNET-SL Register Devices in slave PLC program Principle of Explicit Message Sending Sending Explicit Message from Ladder DiagramMAC ID Node Address00 DeviceNet Node Address02 H0101 D6250 ReqID = 01, Command = DeviceNet Network Scanner DVPDNET-SL H0008 D6251 Port = 00, Size = PLC Bit-Strobe CommandDisplay of Node Status on Network Display of Node Status in Scan ListPower LED LED Indicator & Trouble-shootingNS LED MS LED MS LEDCorrection is needed Memo