Delta Electronics manual Slave → DVPDNET-SL Register Devices in slave

Page 20

DeviceNet Network Scanner DVPDNET-SL

Slave → DVPDNET-SL

Register in

 

 

Devices in slave

DVPDNET-SL

 

 

 

 

 

D6037H

 

DI/DO module

X0 ~ X7 on DVP-16SP

 

 

 

 

D6037L

 

 

N/A

 

 

 

 

D6038H

 

 

Status of LED on VFD-B

 

 

 

 

D6038L

 

AC motor drive

Status of VFD-B

 

 

 

D6039H

 

High byte of frequency in VFD-B

 

 

 

 

 

Low byte of frequency in VFD-B

D6039L

 

 

 

 

 

 

„If the I/O data include control word and status word of RTU-DNET, the I/O data mapping of DVPDNET-SL and its slave devices will be:

DVPDNET-SL → slave

Register in

 

 

Devices in slave

 

DVPDNET-SL

 

 

 

 

 

 

 

D6287H

 

RTU-DNET

High byte of control word in RTU-DNET

 

D6287L

 

control word

Low byte of control word in RTU-DNET

 

 

 

 

 

 

D6288H

 

DI/DO module

Y0 ~ Y7 on DVP-16SP

 

 

 

 

 

 

D6288L

 

 

N/A

 

 

 

 

 

 

D6289H

 

 

High byte of command in VFD-B

 

D6289L

 

AC motor drive

Low bye of command in VFD-B

 

 

 

 

 

D6290H

 

High byte of frequency in VFD-B

 

 

 

 

 

 

 

 

 

D6290L

 

 

Low byte of frequency in VFD-B

 

 

 

 

 

 

Slave → DVPDNET-SL

 

 

 

 

 

 

 

Register in

 

 

Devices in slave

 

DVPDNET-SL

 

 

 

 

 

 

 

D6037H

 

RTU-DNET

High byte of status word in RTU-DNET

 

D6037L

 

status word

Low byte of status word in RTU-DNET

 

 

 

 

 

 

D6038H

 

DI/DO module

X0 ~ X7 on DVP-16SP

 

 

 

 

 

 

D6038L

 

 

N/A

 

 

 

 

 

 

D6039H

 

 

Status of LED on VFD-B

 

 

 

 

 

 

D6039L

 

AC motor drive

Status of VFD-B

 

D6040H

 

High byte of frequency in VFD-B

 

 

 

 

 

 

 

Low byte of frequency in VFD-B

 

D6040L

 

 

 

 

 

 

 

 

3.Saving the configuration data

Select “File” => “Save” to save the current network configuration.

5.3DeviceNet Network Control

In this section, we will introduce how to compile WPL program and control DeviceNet. The example given below is particularly for I/O data excluding RTU-DNET control word and status word. You will have to slightly modify the example program if the I/O data include RTU-DENT control word and status word.

Target

When X0 = On, VFD-B will start to run, and Y0 indicator will be On. When X1 = On, VFD-B will stop, and Y0 indicator will be Off.

18

DVP-PLC Application Manual

Image 20
Contents DVPDNET-SL Page Table of Contents Display of Node Status in Scan List Status of DVPDNET-SL Digital Indicator LEDPrinciple of Bit-Strobe Features IntroductionI/O Scan List CanDimension Product Profile & OutlineDVPDNET-SL PIN VDC CanlShield CanhIN1 Installing DVPDNET-SL and DVP-SV MPU on DIN RailBasic Operation Configuration Corresponding Relation between DVPDNET-SL and DVP-SVI/O Mapping Table How to Construct a DeviceNet NetworkConstructing DeviceNet Network RTU-DNET Ascii COM1DVP-SV DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DVPDNET-SL Slave → DVPDNET-SL Register Devices in slave PLC program Sending Explicit Message from Ladder Diagram Principle of Explicit Message SendingMAC ID Node Address00 DeviceNet Node Address02 H0101 D6250 ReqID = 01, Command = DeviceNet Network Scanner DVPDNET-SL H0008 D6251 Port = 00, Size = Bit-Strobe Command Display of Node Status on NetworkDisplay of Node Status in Scan List PLCLED Indicator & Trouble-shooting Power LEDMS LED NS LED MS LEDCorrection is needed Memo