DeviceNet Network Scanner DVPDNET-SL 
(4)Program explanations:
In the beginning of the program, clear the response message editing area and request message editing area to 0.
When M0 = On, 
When M0 = On, 
When the reading is successful, the message responded from the target equipment will be stored in D6000 ~ D6003.
5.Application example (II)
Target
M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to “0004Hex”.
(1)The connection
(2) Compulsory settings and explanations on devices  Compulsory settings in 
| 
 | Parameter | Set value | Explanation | 
| 
 | Node address | 00 | Set the node address of  | 
| 
 | 
 | 
 | 
 | 
| 
 | Baud rate | 500kbps | Set the communication speed of  | 
| 
 | “500kbps”. | ||
| 
 | 
 | 
 | |
|  Compulsory settings in IFD9502 | 
 | ||
| 
 | 
 | 
 | 
 | 
| 
 | Parameter | Set value | Explanation | 
| 
 | Node address | 02 | Set the node address of IFD9502 to “02”. | 
| 
 | 
 | 
 | 
 | 
| 
 | Baud rate | 500kbps | Set the communication speed of IFD9502 and bus to | 
| 
 | “500kbps”. | ||
| 
 | 
 | 
 | |
|  Compulsory settings in  | 
 | ||
| 
 | 
 | 
 | 
 | 
| 
 | Parameter | Set value | Explanation | 
| 
 | 04 | The main frequency is operated on  | |
| 
 | 
 | 
 | 
 | 
| 24 |