DeviceNet Network Scanner DVPDNET-SL

3.

Power, MS, NS LED

8.

Function switch

4.

DIN rail clip

9.

DeviceNet connection port

5.Digital indicator

2.3DeviceNet Connection Port

The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with

DVPDNET-SL.

PIN

Signal

Color

Content

 

1

V-

Black

0 VDC

5

2

CAN_L

Blue

Signal-

4

3

SHIELD

-

Shielded

3

2

4

CAN_H

White

Signal+

1

5

V+

Red

24 VDC

 

2.4Address Switch

The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are forbidden).

Switch setting

Content

 

 

0 … 63

Valid DeviceNet node address

 

 

64…99

Invalid DeviceNet node address

 

 

5

4 3

2

 

1

0

 

4

5

 

3

 

2

 

1

0

 

6

7

8 9

6

7

8 9

Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding switch of x101 to 2 and the corresponding switch of x100 to 6.

Note:

zPlease set up the node address when the power is switched off. After the setup is completed, re-power

DVPDNET-SL.

zWhen DVPDNET-SL is operating, changing the setting of node address will be invalid.

zUse slotted screwdriver to rotate the switch carefully in case you scratch the switch.

2.5Function Switch

The function switches are for:

„ Setting up the work mode (IN0)

„ Setting up the baud rate of DeviceNet (DR0 ~ DR1)

DR1

DR0

Baud rate

 

 

 

OFF

OFF

125 kbps

OFF

ON

250 kbps

ON

OFF

500 kbps

ON

ON

Incorrect setting

IN0

ON

When the slave is off-line, the I/O data in

the buffer area will be held.

 

 

6

DVP-PLC Application Manual

Image 8
Contents DVPDNET-SL Page Table of Contents Display of Node Status in Scan List Status of DVPDNET-SL Digital Indicator LEDPrinciple of Bit-Strobe Features IntroductionI/O Scan List CanDimension Product Profile & OutlineDVPDNET-SL PIN VDC CanlShield CanhIN1 Installing DVPDNET-SL and DVP-SV MPU on DIN RailBasic Operation Configuration Corresponding Relation between DVPDNET-SL and DVP-SVI/O Mapping Table How to Construct a DeviceNet NetworkConstructing DeviceNet Network RTU-DNET Ascii COM1DVP-SV DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DVPDNET-SL Slave → DVPDNET-SL Register Devices in slave PLC program Sending Explicit Message from Ladder Diagram Principle of Explicit Message SendingMAC ID Node Address00 DeviceNet Node Address02 H0101 D6250 ReqID = 01, Command = DeviceNet Network Scanner DVPDNET-SL H0008 D6251 Port = 00, Size = Bit-Strobe Command Display of Node Status on NetworkDisplay of Node Status in Scan List PLCLED Indicator & Trouble-shooting Power LEDMS LED NS LED MS LEDCorrection is needed Memo