Siemens OSM, ESM technical specifications Select/Set Button

Page 65

Interfaces, Displays and Operator Controls

4.2.4.2"Select/Set" Button

The "Select/Set" button on the front panel of the OSM/ESM has the following functions:

Pressing the button briefly moves on the display of the port LEDs (display mode). The current display mode is indicated by the display mode LEDs.

If the display is in the port status (all display mode LEDs off) and if the button is pressed for three seconds, the display mode LEDs begin to flash. If you then continue to press the button for a further two seconds, the OSM/ESM is reset.

When it is reset, all the settings of the OSM/ESM are set to their defaults (as set in the factory). This allows you to cancel settings made, for example, with Web-Based Management (WBM) (see also OSM/ESM Network Management, User Manual).

If the display is in the fault mask status and you press the button for two seconds, the display LEDs start to flash. If you then press the button for a further two seconds, the current status of the ports and the supply voltages are entered in the fault mask. This means, if, for example, the ports 1, 5, 6 had a valid connection (in other words the port status displays of these ports are lit green or yellow) and if power supply 1 was active at the point when the values were entered in the fault mask, ports 1, 5, 6 and power supply 1 will then be monitored.

Note

If the "Select/Set" button is pressed while the device is starting up (takes approximately 20 seconds) after turning on the OSM/ESM, the OSM/ESM changes to the load firmware status (all display mode LEDs flash simultaneously). This status is exited by pressing the button again. For further information on loading the firmware, refer to Chapter 6.

Industrial Ethernet OSM/ESM

61

C79000-Z8976-C068-10

Image 65
Contents Simatic NET Copyright Siemens AG 2000/02, All rights reserved Classification of Safety-Related NoticesTrademarks Safety Instructions Regarding your ProductQualified Personnel Correct Usage of Hardware ProductsPrior to Startup Correct Usage of Software ProductsPreface Installing an OSM/ESMPurpose of the Operating Instructions PackageFinding Information Validity of the Operating InstructionsFurther Documentation Audience Guide to the ManualPersonnel Qualification Requirements Standards and ApprovalsContents Introduction Introduction Possible Attachments Overview of the Variants of the OSM/ESMOSM ITP62 Properties of the OSM ITP62 OSM ITP62-LD OSM ITP62-LDITP62-LD Properties of the OSM ITP62-LDOSM ITP53 OSM ITP53Properties of the OSM ITP53 ESM ITP80 ESM ITP80Properties of the ESM ITP80 OSM TP62 OSM TP62Properties of the OSM TP62 ESM TP80 ESM TP80Properties of the ESM TP80 OSM BC08 OSM BC08Properties of the OSM BC08 OSM TP22 OSM TP22Properties of the OSM TP22 ESM TP40 ESM TP40Properties of the ESM TP40 Limitation of Errors to the Network Segment Affected Simple Network Configuration and Network ExpansionFunctions Increased Network PerformancePackets with the Vlan Priority Tag Setting the Transmission Rate, AutonegotiationDeleting Addresses Functions Network Topologies with OSM/ESM Bus with OSM Bus StructureBus with ESMs Redundant Ring Structure with OSMs Redundant Ring StructureESM in RM mode Redundant Coupling of Network Segments OSM/ESM Replacing the Standby Master During Operation Port Assignment in the Standby ModeSimultaneous Standby and Redundancy Manager Operation OSM RM mode Compatibility Compatibility of OSM Version 2/ESM with OSM/ORM VersionRing with OSM Version 2 as Redundancy Manager Redundant Coupling of Rings Standby Master Slave OSM Coupling Network Segments OSM RM modeInterfaces, Displays and Operator Controls TP Ports ITP/TP PortsITP Ports Properties of the TP/ITP Ports Autonegotiation ModeLink Control Auto Polarity ExchangeInterfaces, Displays and Operator Controls FO Ports Standby-Sync Port Pinout Serial InterfaceTerminal Block for the Power Supply and Signaling Contact RM Mode additional Power SupplySignaling Contact OSM/ESM in the Standby Mode Input voltage must not exceed +30V DC or fall below -30V DC Digital InputsDisplays and Operator Controls Fault red LEDLED Display Status Stby Standby green LEDRM Redundancy Manager green LED Display mode Meaning LED PowerFault Mask Display Port LEDsFull duplex Port LED DIP Switches Two-Pin DIP SwitchSelect/Set Button Installation, Commissioning, Cleaning Maintenance Unpacking, Checking the Consignment Do not install damaged componentsPreparations InstallationStandard Rail Mounting Installing the OSM on a DIN Standard RailRemoving from the Standard Rail Removing from a Standard RailInstallation on the S7-300 Rail Installation on a Simatic S7-300 RailInstallation in the 19 Cubicle Installation in Pairs in the 19 CubicleWall Mounting Wall MountingWall Mounting Cleaning Maintenance Specifying the keyword OSM Firmware Firmware UpdateFirmware Update Firmware Update Firmware Update Firmware Update Ports Technical SpecificationsTechnical Specifications Cascading Depth Switching Properties of OSM/ESMPermitted Cable Lengths Permitted Ambient Conditions/EMC Only horizontal installationMechanical Design PermittedConsignment / Order Numbers Accessories CE Mark Standards and ApprovalsProduct name Approval for Australia Area of ApplicationUL Approval CSA CertificationFM Approval Adherence to Installation Instructions Glossary Fault Mask Filtering ITP PortTP Port LatencyLink Control Industrial Ethernet OSM/ESM C79000-Z8976-C068-10 Http//www4.ad.siemens.de/view/cs/de/8677203 ReferencesIndustrial Ethernet OSM/ESM C79000-Z8976-C068-10 Ambient conditions, permitted IndexIndex