Siemens Module B3 manual Disturbance Variable z, Setpoint Value w, Comparing Element

Page 9

Automation and Drives - SCE

4. The Disturbance Variable z

The disturbance variable is the variable that unintentionally influences the controlled variable, and moves it from the current setpoint value. A fixed setpoint control is necessary, for example, because a disturbance variable exists. For the heating system considered here, this would be the outside temperature, for example, or any other variable that changes the room temperature from its ideal value.

5. The Setpoint Value w

The setpoint value at a point in time is the value that the controlling variable should ideally have at that time. It should be noted that the setpoint value can change continuously under certain circumstances if there is a slave value control. The measured value that the measuring device used would establish if the controlled variable would have exactly the setpoint value is the instantaneous value of the reference variable. In the example, the setpoint value would be the room temperature desired at that time.

6. The Comparing Element

This is the point where the current measured value of the controlled variable and the instantaneous value of the reference variable are compared. In most cases, both variables are measured circuit voltages. The difference of both variables is the “control deviation“ e. It is passed on to the controlling element, and evaluated there (see below).

7. The Controlling Element

The controlling element is the actual center piece of a control system. It evaluates the system deviation -that is, the information about whether, how and to what extent the controlled variable deviates from the current setpoint- as input information, and derives from this the

“Controller output variable“ YR which, ultimately, influences the controlled variable. The controller output variable would be, in the example of the heating system, the voltage for the mixer motor. The manner in which the controlling element determines the controller output variable from the system deviation is the main criterion of the control system. Part II discusses this topic in greater detail.

 

Preface

Fundamentals

Discontinuous Action Controller Controller Block (S)FB41

Setting the System Appendix

 

 

 

 

 

 

 

T I A Training Document

Page 9 of 64

Module

 

 

 

 

B3

Issued: 02/2008

 

 

Control Engineering with STEP 7

Image 9
Contents Module B3 Automation and Drives SCE Table of Contents Automation and Drives SCE Frequency Converter at Simatic S7 To 3 days Module C To 3 days Module DLearning Objective PrerequisitesPLC Hardware and software requiredTasks of Control Engineering Fundamentals of Control EngineeringComponents of a Control Loop Controlled VariableFeedback Variable r Setpoint Value w Disturbance Variable zComparing Element Controlling ElementActuator Controlled SystemDead Time Characteristics Step Function for Examining Controlled Systems ForAutomation and Drives SCE Time constant Proportional Controlled System with a Time DelayProportional Controlled System with Two Time Delays Tu Delay time Tg Transition timeControllability of P-Tn systems Proportional Controlled System with n Time Delays Controlled Systems without Inherent Regulation Types of Controllers Two Position Controllers Hysteresis Switch-On Value Manipulated Variable TimeThree Position Controllers Basic Types of Continuous Controllers Proportional Controllers P-Controller Automation and Drives SCE Integral Action Controllers I- Controller WithController Layout PI ControllersPID Controllers Derivative Action Controllers D-ControllerObjectives for Controller Adjustment 450.85 Digital Controllers DAC Preface Fundamentals YES StructogramExercise Assignment List Symbol Address CommentNetwork Possible Solution for the PLC ProgramD24/AIFillSetpNorm/Norm.value for level setpoint Network 10 Title Task Definition for PID Standard Controller Function Diagram of the control system with a PID controller FB 41 Contc UseDescription Exercise Example Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE SP INT PLC’ Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE General Tu-TgApproximationT g Approximation Setting the PI-Controller according to Ziegler-Nichols For setpoint characteristic MAN Solution of the PLC program Setpoint Setting the PI controller according to Ziegler-NicholsAppendix Diagram of the controller blockComrst Bool False Input Parameters Data Value Range Default Description TypeParameter Data Type Value Range Default Lmnhlm Real Lmnllm Output Parameters Parameter Data Value Range Default Description Type