Input Parameters

 

 

 

 

 

 

 

 

Parameter

Data

Value Range

Default

Description

 

Type

 

 

 

COM_RST

BOOL

 

FALSE

COMPLETE RESTART. The block has a

 

complete restart routine that is processed if the

 

 

 

 

 

 

 

 

input is set to "Complete restart".

 

 

 

 

 

MAN_ON

BOOL

 

TRUE

MANUAL VALUE ON / Switch on manual

 

 

 

 

operation. If the input "switch on manual

 

 

 

 

operation" is set, the control loop has been

 

 

 

 

interrupted. A manipulated value is entered as

 

 

 

 

manual value.

PVPER_ON

BOOL

 

FALSE

PROCESS VARIABLE PERIPHERY ON /

 

 

 

 

Actual value

 

 

 

 

Switch on the periphery. If the periphery is to

 

 

 

 

read in the actual value, input PV_PER has to

 

 

 

 

be wired to the periphery, and the input "Switch

 

 

 

 

on actual value periphery" has to be set.

 

 

 

 

 

P_SEL

BOOL

 

TRUE

PROPORTIONAL ACTION ON / Switch on P-

 

 

 

 

component. In the PID algorithm, the PID

 

 

 

 

components can be switched on/off individually.

 

 

 

 

The P-component is switched on if the input

 

 

 

 

"Switch on P-component" is set.

I_SEL

BOOL

 

TRUE

INTEGRAL ACTION ON / Switch on I-

 

 

 

 

component. In the PID algorithm, the PID

 

 

 

 

components can be switched on/off individually.

 

 

 

 

The I-component is switched on if the input

 

 

 

 

"Switch on I- component" is set.

 

 

 

 

 

INT_HOLD

BOOL

 

FALSE

INTEGRAL ACTION HOLD / Freeze I-

 

 

 

 

component. The output of the integrator can be

 

 

 

 

frozen. To this end, the input "Freeze I-

 

 

 

 

component“ is set.

 

 

 

 

 

I_ITL_ON

BOOL

 

FALSE

INITIALIZATION OF THE INTEGRAL ACTION /

 

 

 

 

Set I-component. The output of the integrator

 

 

 

 

can be set to the input I_ITL_VAL. To this end,

 

 

 

 

the input "Set I-component“ has to be set.

 

 

 

 

 

D_SEL

BOOL

 

FALSE

DERIVATIVE ACTION ON / Switch on D-

 

 

 

 

component. In the PID algorithm, the PID

 

 

 

 

components can be switched on/off individually.

 

 

 

 

The D-component is switched on if the input

 

 

 

 

"Switch on D-component" is set.

 

Preface Fundamentals

Discontinuous Action Controller Controller Block (S)FB41

Setting the System Appendix

 

 

 

 

 

 

 

T I A Training Document

Page 61 of 64

Module

 

 

 

B3

Issued: 02/2008

 

Control Engineering with STEP 7

Image 61
Contents Module B3 Automation and Drives SCE Table of Contents Automation and Drives SCE Frequency Converter at Simatic S7 To 3 days Module C To 3 days Module DLearning Objective PrerequisitesPLC Hardware and software requiredTasks of Control Engineering Fundamentals of Control EngineeringControlled Variable Components of a Control LoopFeedback Variable r Setpoint Value w Disturbance Variable zComparing Element Controlling ElementControlled System ActuatorDead Time Characteristics Step Function for Examining Controlled Systems ForAutomation and Drives SCE Time constant Proportional Controlled System with a Time DelayTu Delay time Tg Transition time Proportional Controlled System with Two Time DelaysControllability of P-Tn systems Proportional Controlled System with n Time Delays Controlled Systems without Inherent Regulation Types of Controllers Two Position Controllers Hysteresis Switch-On Value Manipulated Variable TimeThree Position Controllers Basic Types of Continuous Controllers Proportional Controllers P-Controller Automation and Drives SCE Integral Action Controllers I- Controller WithController Layout PI ControllersPID Controllers Derivative Action Controllers D-ControllerObjectives for Controller Adjustment 450.85 Digital Controllers DAC Preface Fundamentals YES StructogramExercise Assignment List Symbol Address CommentNetwork Possible Solution for the PLC ProgramD24/AIFillSetpNorm/Norm.value for level setpoint Network 10 Title Task Definition for PID Standard Controller Function Diagram of the control system with a PID controller Use FB 41 ContcDescription Exercise Example Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE SP INT PLC’ Automation and Drives SCE Automation and Drives SCE Automation and Drives SCE Tu-TgApproximation GeneralT g Approximation Setting the PI-Controller according to Ziegler-Nichols For setpoint characteristic MAN Solution of the PLC program Setpoint Setting the PI controller according to Ziegler-NicholsAppendix Diagram of the controller blockComrst Bool False Input Parameters Data Value Range Default Description TypeParameter Data Type Value Range Default Lmnhlm Real Lmnllm Output Parameters Parameter Data Value Range Default Description Type