KTI Networks KSC-240 manual RS-485 Full-duplex 4-wire Network

Page 39

The converter features RS-485 driver and receiver in one device. It also provides very flexible configuration settings for Driver Enable control and Receiver Enable control. The configuration for the node in RS-485 2- wire network is:

SW1-2&1

2W

Select 2-wire topology

SW1-4

TXC

Enable RTS/ADC Control for Driver

SW1-6

RXC

Enable RTS/ADC Control for Receiver

SW1-5

RTS-E

Use RTS control (optional)

SW2-1

SDE

Use ADC control (optional)

SW2-2-8

Baud

Baud when ADC control is enabled (optional)

SW1-3

T-D

Disable internal terminator (optional)

3.5 RS-485 Full-duplex 4-wire Network

The 4-wire network simplifies bus arbitration in multi-node RS-485. A single Master node is the only driver allowed on the top most wire pair. All other nodes listen to all data traffic that passes on the party-line type multi-drop bus. Nodes may transmit on the lower pair of wires when addressed by the master node or by using a software token-passing bus arbitration scheme.

-39-

Image 39
Contents Industrial RS-232 to RS-485/422 Converter KSC-240 Installation GuideInternational United StatesEthernet is a registered trademark of Xerox Corp Table of Contents Introduction Features Specifications LEDIndicators Serial Interface RS-232 PortRS-485/422 Interface Name State Function Configuration DIP SW SettingsEnvironmental DC Power InterfaceBasic Information MechanicalCE/EMC CertificateUnpacking InstallationSafety Cautions DIN-Rail Mounting Page Panel Mounting Screw locations and final dimension are shown below Using Terminal Blocks Applying PowerPage UsingDC Power Jack Power Failure Relay Output SW1-2 DIP SW ConfigurationSW1-3 TXE SW1-4SW1-6 SW1-5SW1-8&7 SW2-4 SW2-1SW2-2 SW2-3SW1-4 SW1-6 SW1-5 SW2-1 Behavior 1 RS-485/422 Driver and Receiver ControlTypical RS-232 Interface DCE Pin Assignment Table Making Serial RS-232 ConnectionSignal Name Input/Output Cable for Connection to PC COM Port Making RS-485/422 Connection Characteristics RS-422 RS-485RS-422 Point-to-Point Circuit RS-422 Multi-drop Network TXE RS-485 Multi-drop Network TXC RS-485 Half-duplex 2-wire Network RS-485 Full-duplex 4-wire Network Or use ADC control optional Summary of the Converter Applications LED Indicators Name Default Setting Factory Default Configuration