Page 12

Steel Ventilated Trough

The 1999 NEC® added the word ‘ventilated’ in front of trough to clear up some confusion that solid trough is treated the same as ventilated trough. It is not. Solid trough is recognized as solid bottom cable tray.

Ventilated trough cable tray is often used when the specifier does not want to use ladder cable tray to support small diameter multiconductor control and instrumentation cables. As no drooping of the small diameter cables is visible, ventilated trough cable trays provide neat appearing installations. Small diameter cables may exit the ventilated trough cable tray through the bottom ventilation holes as well as out the top of the cable tray. For installations where the cables exit the bottom of the cable tray and the system is subject to some degree of vibration, it is advisable to use B-Line Trough Drop-Out Bushings (Cat. No. 99-1124). These snap-in bushings provide additional abrasion protection for the cable jackets. Just as for ladder cable tray, ventilated trough cable tray will not pipe moisture into electrical equipment.

Standard widths for ventilated trough cable tray systems are 6, 9, 12, 18, 24, 30, and 36 inches. The standard bottom configuration for ventilated trough cable tray is a corrugated bottom with 2 7/8 inch bearing surfaces - 6 inches on centers and 2 1/4 inch x 4 inch ventilation openings. Since a corrugated bottom cannot be bent horizontally, the standard bottom configuration for horizontal bend fittings consists of rungs spaced on 4 inch centers. This difference in bottom construction may be objectionable to some owners, so be sure you are aware of the owner's sensitivity to aesthetics for the cable tray installation.

Vent. Channel Cable Tray

(B-Line's Cable Channel)

Cooper B-Line, Inc

Channel cable tray systems (B-Line's cable channel) are available in 3, 4, and 6 inch widths with ventilated or solid bottoms. The 2002 NEC® now recognizes solid bottom cable channel. Prior to the 2002 Code, the NEC® did not have any specific provisions for the use of solid cable channel.

Instead of large conduits, cable channel may be used very effectively to support cable drops from the cable tray run to the equipment or device being serviced and is ideal for cable tray runs involving a small number of cables. Cable channel may also be used to support push buttons, field mounted instrumentation devices, etc. Small diameter cables may exit ventilated cable channel through the bottom ventilation holes, out the top or through the end. For installations where the cables exit through the ventilation openings and the cable channel or the cables are subject to some degree of vibration, it is advisable to use B-Line Cable Channel Bushings (Cat. No. 99-1125). These snap-in plastic bushings provide additional abrasion protection for the cable jackets.

Aluminum Solid Bottom Trough

Some specifiers prefer solid bottom cable tray to support large numbers of small diameter control and multiconductor instrumentation cables. Solid bottom steel cable trays with solid covers and wrap around cover clamps can be used to provide EMI/RFI shielding protection for sensitive circuits.

Unlike ladder and ventilated trough cable trays, solid bottom cable trays can collect and retain moisture. Where they are installed outdoors or indoors in humid locations and EMI/RFI shielding protection is not required, it is recommended that 1/4 inch weep holes be drilled in their bottoms at the sides and in the middle every 3 feet to limit water accumulation.

Cable Tray Manual

10

Image 12
Contents Cable Tray Manual Page Table of Contents Introduction WHY Cable TRAY? Cable Tray Safety FeaturesCable Tray Dependability Cable Tray Space SavingsCable Tray Wiring System Cost Savings Design Cost SavingsMaterial Cost Savings Installation Cost Time Savings Cost Cable Tray vs. ConduitMaintenance Savings Cooper B-Line, Inc AN IN-DEPTH Look AT 2002 NEC Article 392 Cable Tray ScopeSteel Ventilated Trough Center Supported Cable Tray Uses Permitted. a Wiring Methods Cable Tray MaterialsDefinition. Cable Tray System Cable Tray Manual Uses Permitted. B In Industrial Establishments 392.3B1a 392.3B1b392.3B1c Uses Permitted. C Equipment Grounding ConductorsSealing and Drainage. E Cable Seals, Class 1, Division 2 502.4B3. Nonincendive Field Wiring Uses Permitted. E Nonmetallic Cable TrayConstruction Specifications. a Strength and Rigidity Uses Not PermittedCable Tray Manual Construction Specifications. B Smooth Edges Construction Specifications. C Corrosion ProtectionConstruction Specifications. D Side Rails Construction Specifications. E FittingsConstruction Specifications. F Nonmetallic Cable Tray Installation. a Complete SystemNomenclature Installation. B Completed Before Installation Installation. C Supports Installation. D CoversInstallation. G Through Partitions and Walls Installation. F Cables Over VoltsInstallation. H Exposed and Accessible Installation. I Adequate Access Grounding. a Metallic Cable Trays EGC Grounding. B Steel or Aluminum Cable Tray Systems Temperature Rise Test Cable Installation. a Cable Splices Cable Installation. B Fastened SecurelyCable installation. C Bushed Conduit and Tubing Cable Installation. D Connected in ParallelSheet 3, Example 392.9A1 392.9A2 392.9E2 392.9F2 Single Diameter Inch Conductor Inches Channel Size AWG Technically Undesirable Installation Interpretation #1 Cable Tray Wiring System Design and Installation Hints Cable Tray Manual Cooper B-Line, Inc Cable Tray Accessories Cable Tray Maintenance and RepairFireproofing Cable Tray Cable TRAY. Thermal Contraction and Expansion FRP13B is 128 F. The 125 F line in Table Cable Tray Manual Cooper B-Line, Inc Appendix Pages See Page 29 for Temperature Rise Test illustration Circuit Arrangement for Rigid Conduit Temperature Rise Tests Example NEC .9A1 Example NEC .9A2 Example NEC .9A3 Example NEC .9B Appendix Sheet Cable Tray Sizing Flowchart Start Sizing Cable Tray Per NEC HereYes Ladder Or Vented Trough Project Information Fiberglass-Vinyl Ester ResinLine Series Wire Basket Tray Cable ChannelVentilated Non-Ventilated Cent-R-Rail Cooper B-Line, Inc Cable Tray Manual Line Wire Management Resources Ask the Experts