Cooper Bussmann CT02MAN manual Yes Ladder Or Vented Trough

Page 55

CABLE TRAY SIZING FLOWCHART

Ampacity: See pages 36 - 38 for information on cable ampacity that might affect the cable tray sizing flowchart.

See pages 15 - 17 for information on hazardous (classified) areas that might affect the cable tray sizing flowchart.

Yes

Ladder

 

 

No

or Vented

 

 

 

 

 

 

 

 

 

 

Trough

 

 

 

 

 

 

 

Tray

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M/C 4/0

Yes

392.9(A)(1)

 

 

 

 

 

W ≥ Sd

 

 

 

or larger

 

 

 

 

 

 

 

(single layer)

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solid

 

 

No

Vented

 

No

Solid

Bottom

 

 

 

 

 

Channel

 

 

 

 

Channel

 

 

 

 

 

 

 

 

 

Tray

 

 

 

 

Tray

 

 

 

 

Tray

 

Yes

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M/C 4/0

Yes

392.9(C)(1)

 

One M/C

Yes

392.9(E)(1)

W ≥ Sd/0.9

 

or larger

 

 

 

only

 

 

 

 

W x D ≥ 1.6A

 

 

(single layer)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M/C

Yes

 

392.9(A)(2)

 

smaller

 

 

 

 

 

 

 

W ≥ A/1.2

 

 

 

 

 

than 4/0

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M/C

Yes

 

392.9(A)(3)

smaller than

 

 

 

4/0, with

 

 

W ≥ A/1.2 + Sd

 

 

4/0 or

 

 

larger

 

 

 

 

 

Note: The value “A” only applies to cables smaller than 4/0.

No The value “Sd” only applies to 4/0 and larger cables, which must be single layer

M/C

Yes

392.9(B)

control

 

 

 

and/or

 

 

W x D ≥ 2A

signal

 

 

 

 

 

M/C

Yes

392.9(C)(2)

 

smaller

 

 

 

 

 

 

 

W ≥ A/0.9

 

 

 

 

 

than 4/0

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

392.9(C)(3)

M/C

Yes

smaller than

 

 

 

4/0, with

 

 

W ≥

A + Sd

 

 

4/0 or

 

 

 

 

 

larger

 

 

0.9

 

Note: The value “A” only applies to cables smaller than 4/0.

No The value “Sd” only applies to 4/0 and larger cables, which must be single layer

M/C Yes

392.9(D)

control

 

 

 

and/or

 

 

W x D ≥ 2.5A

signal

 

392.9(E)(2)

No

One

 

 

M/C

W x D ≥ 2.9A

 

 

 

 

Only

 

 

 

Yes

392.9(F)(2)

392.9(F)(1)

W x D ≥ 3.2A

W x D ≥ 1.9A

Legend

W = Cable Tray Width

D = Cable Tray Load Depth Sd = Sum of Cable Diameters A = Sum of Cable Areas S/C = Single Conductor M/C = Multiconductor Cables RS = Ladder Rung Spacing

Cable Tray Manual

Appendix Sheet 8

Cooper B-Line, Inc

53

Image 55
Contents Cable Tray Manual Page Table of Contents Introduction Cable Tray Safety Features WHY Cable TRAY?Cable Tray Space Savings Cable Tray DependabilityDesign Cost Savings Cable Tray Wiring System Cost SavingsMaterial Cost Savings Cost Cable Tray vs. Conduit Installation Cost Time SavingsMaintenance Savings Cooper B-Line, Inc Scope AN IN-DEPTH Look AT 2002 NEC Article 392 Cable TraySteel Ventilated Trough Center Supported Cable Tray Cable Tray Materials Uses Permitted. a Wiring MethodsDefinition. Cable Tray System Cable Tray Manual Uses Permitted. B In Industrial Establishments Uses Permitted. C Equipment Grounding Conductors 392.3B1a392.3B1b 392.3B1cSealing and Drainage. E Cable Seals, Class 1, Division 2 Uses Permitted. E Nonmetallic Cable Tray 502.4B3. Nonincendive Field WiringUses Not Permitted Construction Specifications. a Strength and RigidityCable Tray Manual Construction Specifications. E Fittings Construction Specifications. B Smooth EdgesConstruction Specifications. C Corrosion Protection Construction Specifications. D Side RailsInstallation. a Complete System Construction Specifications. F Nonmetallic Cable TrayNomenclature Installation. B Completed Before Installation Installation. D Covers Installation. C SupportsInstallation. F Cables Over Volts Installation. G Through Partitions and WallsInstallation. H Exposed and Accessible Installation. I Adequate Access Grounding. a Metallic Cable Trays EGC Grounding. B Steel or Aluminum Cable Tray Systems Temperature Rise Test Cable Installation. B Fastened Securely Cable Installation. a Cable SplicesCable Installation. D Connected in Parallel Cable installation. C Bushed Conduit and TubingSheet 3, Example 392.9A1 392.9A2 392.9E2 392.9F2 Single Diameter Inch Conductor Inches Channel Size AWG Technically Undesirable Installation Interpretation #1 Cable Tray Wiring System Design and Installation Hints Cable Tray Manual Cooper B-Line, Inc Cable Tray Maintenance and Repair Cable Tray AccessoriesFireproofing Cable Tray FRP Cable TRAY. Thermal Contraction and Expansion13B is 128 F. The 125 F line in Table Cable Tray Manual Cooper B-Line, Inc Appendix Pages See Page 29 for Temperature Rise Test illustration Circuit Arrangement for Rigid Conduit Temperature Rise Tests Example NEC .9A1 Example NEC .9A2 Example NEC .9A3 Example NEC .9B Appendix Sheet Start Sizing Cable Tray Per NEC Here Cable Tray Sizing FlowchartYes Ladder Or Vented Trough Fiberglass-Vinyl Ester Resin Project InformationLine Series Cable Channel Wire Basket TrayVentilated Non-Ventilated Cent-R-Rail Cooper B-Line, Inc Cable Tray Manual Line Wire Management Resources Ask the Experts