Cooper Bussmann CT02MAN manual Installation. B Completed Before Installation

Page 24

There are some designers, engineers, and inspectors that do not think that cable tray is a mechanical support system just as strut is a mechanical support system. Cable tray is not a raceway in the NEC® but some designers, engineers, and inspectors attempt to apply the requirements for raceway wiring systems to cable tray wiring systems even when they are not applicable. Cable tray wiring systems have been used by American industry for over 35 years with outstanding safety and continuity of service records. The safety service record of cable tray wiring systems in industrial facilities has been significantly better than those of conduit wiring systems. There have been industrial fires and explosions that have occurred as a direct result of the wiring system being a conduit wiring system. In these cases, cable tray wiring systems would not have provided the fires and explosions that the conduit systems did by providing as explosion gas flow path to the ignition source even though the conduit systems contained seals.

The most significant part of this section is that the metallic cable tray system must have electrical continuity over its entire length and that the support for the cables must be maintained. These requirements can be adequately met even though there will be installation conditions where the cable tray is mechanically discontinuous, such as at a firewall penetration, at an expansion gap in a long straight cable tray run, where there is a change in elevation of a few feet between two horizontal cable tray sections of the same run, or where the cables drop from an overhead cable tray to enter equipment. In all these cases, adequate bonding jumpers must be used to bridge the mechanical discontinuity.

Control Cable Entering Pushbutton and Power Cable Entering Motor Terminal Box from 6 Inch Channel Cable Tray System

(Bottom entries provide drip loops to prevent moisture flow into enclosures.)

Cooper B-Line, Inc

Cables Exiting 480 Volt Outdoor Switchgear and Entering Cable Tray System

(Cable fittings with clamping glands are required to prevent moisture flow into equipment due to the cable's overhead entry into the switchgear enclosure).

Cables Entering and Exiting Motor Control Centers from Cable Tray Systems.

392.6.Installation. (B) Completed Before Installation.

This means that the final cable tray system must be in place before the cables are installed. It does not mean that the cable tray must be 100% mechanically continuous. The electrical bonding of the metallic cable tray system must be complete before any of the circuits in the cable tray system are energized whether the cable tray system is being utilized as the equipment grounding conductor in qualifying installations or if the bonding is being done to satisfy the requirements of Section 250.96.

Cable Tray Manual

22

Image 24
Contents Cable Tray Manual Page Table of Contents Introduction WHY Cable TRAY? Cable Tray Safety FeaturesCable Tray Dependability Cable Tray Space SavingsCable Tray Wiring System Cost Savings Design Cost SavingsMaterial Cost Savings Installation Cost Time Savings Cost Cable Tray vs. ConduitMaintenance Savings Cooper B-Line, Inc AN IN-DEPTH Look AT 2002 NEC Article 392 Cable Tray ScopeSteel Ventilated Trough Center Supported Cable Tray Uses Permitted. a Wiring Methods Cable Tray MaterialsDefinition. Cable Tray System Cable Tray Manual Uses Permitted. B In Industrial Establishments 392.3B1a 392.3B1b392.3B1c Uses Permitted. C Equipment Grounding ConductorsSealing and Drainage. E Cable Seals, Class 1, Division 2 502.4B3. Nonincendive Field Wiring Uses Permitted. E Nonmetallic Cable TrayConstruction Specifications. a Strength and Rigidity Uses Not PermittedCable Tray Manual Construction Specifications. B Smooth Edges Construction Specifications. C Corrosion ProtectionConstruction Specifications. D Side Rails Construction Specifications. E FittingsConstruction Specifications. F Nonmetallic Cable Tray Installation. a Complete SystemNomenclature Installation. B Completed Before Installation Installation. C Supports Installation. D CoversInstallation. G Through Partitions and Walls Installation. F Cables Over VoltsInstallation. H Exposed and Accessible Installation. I Adequate Access Grounding. a Metallic Cable Trays EGC Grounding. B Steel or Aluminum Cable Tray Systems Temperature Rise Test Cable Installation. a Cable Splices Cable Installation. B Fastened SecurelyCable installation. C Bushed Conduit and Tubing Cable Installation. D Connected in ParallelSheet 3, Example 392.9A1 392.9A2 392.9E2 392.9F2 Single Diameter Inch Conductor Inches Channel Size AWG Technically Undesirable Installation Interpretation #1 Cable Tray Wiring System Design and Installation Hints Cable Tray Manual Cooper B-Line, Inc Cable Tray Accessories Cable Tray Maintenance and RepairFireproofing Cable Tray Cable TRAY. Thermal Contraction and Expansion FRP13B is 128 F. The 125 F line in Table Cable Tray Manual Cooper B-Line, Inc Appendix Pages See Page 29 for Temperature Rise Test illustration Circuit Arrangement for Rigid Conduit Temperature Rise Tests Example NEC .9A1 Example NEC .9A2 Example NEC .9A3 Example NEC .9B Appendix Sheet Cable Tray Sizing Flowchart Start Sizing Cable Tray Per NEC HereYes Ladder Or Vented Trough Project Information Fiberglass-Vinyl Ester ResinLine Series Wire Basket Tray Cable ChannelVentilated Non-Ventilated Cent-R-Rail Cooper B-Line, Inc Cable Tray Manual Line Wire Management Resources Ask the Experts