Cooper Bussmann CT02MAN manual Appendix Sheet

Page 53

Table 250.122. Minimum Size Equipment Grounding

Conductors for Grounding Raceways and Equipment

Rating or Setting of

 

Size

Automatic Overcurrent

(AWG or kcmil)

Device in Circuit Ahead

 

 

of Equipment, Conduit,

 

Aluminum or

etc., Not Exceeding

 

Copper-Clad

(Amperes)

Copper

Aluminum*

15

14

12

20

12

10

30

10

8

40

10

8

60

10

8

100

8

6

200

6

4

300

4

2

400

3

1

500

2

1/0

600

1

2/0

800

1/0

3/0

1000

2/0

4/0

1200

3/0

250

1600

4/0

350

2000

250

400

2500

350

600

3000

400

600

4000

500

800

5000

700

1200

6000

800

1200

Reprinted with permission from NFPA 70-1999, the National Electrical Code®, Copyright© 1998, National Fire

Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National

Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.

 

Appendix Sheet 7

Cable Tray Manual

Cooper B-Line, Inc

51

Image 53
Contents Cable Tray Manual Page Table of Contents Introduction Cable Tray Safety Features WHY Cable TRAY?Cable Tray Space Savings Cable Tray DependabilityMaterial Cost Savings Cable Tray Wiring System Cost SavingsDesign Cost Savings Cost Cable Tray vs. Conduit Installation Cost Time SavingsMaintenance Savings Cooper B-Line, Inc Scope AN IN-DEPTH Look AT 2002 NEC Article 392 Cable TraySteel Ventilated Trough Center Supported Cable Tray Definition. Cable Tray System Uses Permitted. a Wiring MethodsCable Tray Materials Cable Tray Manual Uses Permitted. B In Industrial Establishments 392.3B1b 392.3B1a392.3B1c Uses Permitted. C Equipment Grounding ConductorsSealing and Drainage. E Cable Seals, Class 1, Division 2 Uses Permitted. E Nonmetallic Cable Tray 502.4B3. Nonincendive Field WiringUses Not Permitted Construction Specifications. a Strength and RigidityCable Tray Manual Construction Specifications. C Corrosion Protection Construction Specifications. B Smooth EdgesConstruction Specifications. D Side Rails Construction Specifications. E FittingsNomenclature Construction Specifications. F Nonmetallic Cable TrayInstallation. a Complete System Installation. B Completed Before Installation Installation. D Covers Installation. C SupportsInstallation. H Exposed and Accessible Installation. G Through Partitions and WallsInstallation. F Cables Over Volts Installation. I Adequate Access Grounding. a Metallic Cable Trays EGC Grounding. B Steel or Aluminum Cable Tray Systems Temperature Rise Test Cable Installation. B Fastened Securely Cable Installation. a Cable SplicesCable Installation. D Connected in Parallel Cable installation. C Bushed Conduit and TubingSheet 3, Example 392.9A1 392.9A2 392.9E2 392.9F2 Single Diameter Inch Conductor Inches Channel Size AWG Technically Undesirable Installation Interpretation #1 Cable Tray Wiring System Design and Installation Hints Cable Tray Manual Cooper B-Line, Inc Fireproofing Cable Tray Cable Tray AccessoriesCable Tray Maintenance and Repair FRP Cable TRAY. Thermal Contraction and Expansion13B is 128 F. The 125 F line in Table Cable Tray Manual Cooper B-Line, Inc Appendix Pages See Page 29 for Temperature Rise Test illustration Circuit Arrangement for Rigid Conduit Temperature Rise Tests Example NEC .9A1 Example NEC .9A2 Example NEC .9A3 Example NEC .9B Appendix Sheet Start Sizing Cable Tray Per NEC Here Cable Tray Sizing FlowchartYes Ladder Or Vented Trough Line Series Project InformationFiberglass-Vinyl Ester Resin Ventilated Non-Ventilated Cent-R-Rail Wire Basket TrayCable Channel Cooper B-Line, Inc Cable Tray Manual Line Wire Management Resources Ask the Experts