Whole-U Alignment

Half-U Alignment

rack adapter rail rack vertical rail

conical washer

10-32 x 0.375-inch countersunk screws

1-U spacing mark

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿4￿￿!￿&￿￿(￿￿￿￿4￿￿￿￿+￿6￿￿￿￿￿9￿￿￿￿￿3￿￿￿￿9￿

&￿￿￿￿-￿￿￿

d.At the back of the rack, secure the rack adapter rail to the rack’s vertical rail using two 10-32 x 0.375-inch screws and conical washers.

If you used hole numbers 1 and 5 at the front of the rack, hole numbers 8 and 10 will align to holes on the vertical rail (for whole-U alignment).

If you used hole numbers 2 and 6 at the front of the rack, hole numbers 7 and 9 will align to holes on the vertical rail (for half-U alignment). See Figure 2-3.

e.Using a torque-measuring wrench, tighten the rack adapter rail to the vertical rail to 27 inch pounds (3.0 newton meters).

Figure 2-4 shows the rack adapter rails properly positioned in the rack.

2-6 Dell PowerVault 720N, 740N, and 760N Installation and Troubleshooting Guide

Image 36
Contents Page Page Observe the following warnings while servicing this system 006 Vii Viii #$% #-%% #+%$ Page Xiii Xiv Monospaced font Xvi Xvii Xviii Xix Page Xxi Xxii $%$%*$+ Activity LED Status LED Power LED Nostic messages up to 32 characters Describes the back panel features 10/100Base-T Ethernet Disk-Array Enclosure DAE storage system with 18-GB #$!% Slot 9 dedicated to Nvram card $%&# $&#Introduction Page Installing a Filer System +,+ 145=1.75 inch DAA1% 24769!8 Shows the rack adapter rails properly positioned in the rack +6939 Page Installing a Filer System Select any two holes +-0%$ #,,#6233#./$&&# FC-AL1 loop FC-AL0 loop FC-AL adapter in slot $&$2 77% Installing a Filer System #,+ $!1Built-in Ethernet connector 33!# 13 shows the location of the Console port 14 shows two power supplies $&&#AC LED Page 122# Shows the LEDs on the front panel +$ 1# Off-AC signal is not good #1&21 41&21 Quad-port Ethernet card #=# Troubleshooting the Filer Hardware 37# Startup failed Scsi Host Adapter 0b Administrator and Command Reference Storage enclosure address number. Setup Page Filer’s /etc/passwd and /etc/group Mode. Refer to the Dell PowerVault 720N This message appears in these situations Guide System Administrator and Command Ref Page Getting Help Ftp.dell.com Support@us.dell.com Sales@dell.comInfo@dell.com Page Getting Help Diagnostics Checklist 1344 Page Australia AustriaBelgium Brunei CanadaChile ChinaDenmark FinlandFrance Germany Hong KongIreland ItalyJapan KoreaLatin America Luxembourg MacauMalaysia MexicoNetherlands New ZealandNorway PolandSingapore South AfricaSoutheast Asian Pacific CountriesSweden SwitzerlandTaiwan ThailandDell Home and Small Business Group Index Message FC-AL See also Dimms Index Nics Scsi