A rack mounting kit, consisting of:
—Two rack adapter rails and mounting hardware
—A 1/2-U filler panel and mounting hardware (including cage nuts and cage nut installation tool)
—A cable management clip with mounting hardware
+/
)5
Observe the following requirements, cautions, and warnings when you install the filer in a rack (the filer ships with front installation brackets installed).
Ensure that the rack mounting holes meet ANSI/EIA-310-D-92 specifications for 19-inch (483-mm.) wide equipment.
Ensure that equipment installed above the filer is no closer than 0.875-inch (22.2-mm) from the top of the filer’s ventilation holes.
;.-(
%
.-(% .-(
.-(
!"#<=% >?@ AB+ C $
+'
+
!9,DAA1%'
%/(+
1 (
9,DAA
(+
)!%
The left- and right-hand rack adapter rails have six threaded holes on the front and four on the back. The multiple holes allow users to install the rack adapter rails in either whole-unit or half-unit rack mount positions. The six threaded holes are labeled 1 through 6 on the front and 7 through 10 on the back, with stamped numbers.
To install the rack adapter rails in a standard 19-inch (483-mm.) equipment rack, per- form the following steps:
1.Locate marks on the rack’s left and right front vertical rails. These marks are 1-U spacing marks that appear every 1.75 inches of vertical rack height (see Figure 2-1).
2-4 Dell PowerVault 720N, 740N, and 760N Installation and Troubleshooting Guide