VIS-CAM System
6.8.2Connector specification
Connector type: | 8 pole WAGO pluggable terminal block |
Connector on board: | WAGO |
Cable part: | WAGO |
6.8.3Connector signal specifications
6.8.3 (a) Power output
Voltage: | 24 | V DC from power supply connected to X6 or X7 |
| 12 | V DC from regulator on board |
Current: | 0.3A fused |
6.8.3 (b) Databus D0 and D1
D0 and D1 are RS485 databus signals from the light sensor.
6.8.4Connector physical Interface
Table 30 RS485 physical connections
Pin | Signal | Description | Connection to |
|
|
|
|
1 | 24V dc | 24v Power output |
|
|
|
|
|
2 | Gnd | Power return |
|
|
|
|
|
3 | +12V dc | 12V power output |
|
|
|
|
|
4 | Gnd | Power return |
|
|
|
|
|
5 | D0+ | RS485 databus D0+ |
|
|
|
|
|
6 | D0- | RS485 databus D0- |
|
|
|
|
|
7 | D1+ | RS485 databus D1+ |
|
|
|
|
|
8 | D1- | RS485 databus D1+ |
|
|
|
|
|
6.9X11: Ethernet Interface from Camera 0
Figure 77. Interface from Camera 0
6.9.1Functionality
Ethernet interface from Camera 0 to Ethernet switch.
Appendix B: | 77 |