Liebert 1010, 83 Refrigerant Planning Values, R-407C refrigerant required, approximate, Receiver

Page 16

Site Preparation

2.3Refrigerant Planning Values

Planning for the refrigerant requirements of the completed system is the addition of the charges from Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping. Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting piping. Consult indoor unit manuals for indoor unit charge requirements.

These values can be used for obtaining adequate refrigerant for the system, but should not be used for final charging. Consult indoor unit manual for charging procedures.

Table 3

R-22 and R-407C refrigerant required, approximate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Approximate R-22 Refrigerant Needed

Approximate R-407C Refrigerant Needed

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Circuit

 

Dual Circuit

Single Circuit

 

Dual Circuit

 

 

lb (kg)

 

lb/circuit (kg/circuit)

lb (kg)

 

lb/circuit (kg/circuit)

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

Lee-Temp

 

 

Lee-Temp

 

Lee-Temp

 

 

Lee-Temp

Condenser

 

FSC or

(includes

FSC or

(includes

FSC or

(includes

FSC or

(includes

Models

 

VFD

receiver)

VFD

receiver)

VFD

receiver)

VFD

receiver)

83

 

5 (2.3)

27

(12.3)

3

(1.4)

15

(6.8)

5 (2.3)

26

(11.8)

3

(1.4)

15

(6.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

104

 

8 (3.6)

39

(17.7)

7

(3.2)

21

(9.5)

8 (3.6)

37

(16.8)

7

(3.2)

20

(9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

165

 

15 (6.8)

53

(24.0)

5

(2.3)

27 (12.3)

15 (6.8)

50

(22.7)

5

(2.3)

26 (11.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

205

 

20 (9.1)

76

(34.5)

7

(3.2)

38 (17.2)

19 (8.6)

72

(32.7)

7

(3.2)

36 (16.3)

 

 

 

 

 

 

 

 

 

 

 

251

 

19 (8.6)

75

(34.0)

10 (4.6)

38 (17.2)

18 (8.2)

71 (32.23)

10 (4.6)

36 (16.3)

 

 

 

 

 

 

 

 

 

 

308

 

29 (13.2)

113 (51.3)

11 (5.0)

58 (26.3)

28 (12.7)

107 (48.5)

11 (5.0)

55 (24.9)

 

 

 

 

 

 

 

 

 

 

415

 

54 (24.5)

182 (82.6)

15 (6.8)

75 (34.0)

51 (23.1)

173 (78.4)

15 (6.8)

71 (32.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

510

 

72 (32.7)

 

N/A

30

(13.6)

149

(67.6)

68 (30.8)

 

N/A

29

(13.2)

142

(64.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

616

 

N/A

267

(121.3)

27

(12.3)

113

(51.3)

N/A

254

(115.2)

26

(11.8)

108

(49.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

830

 

N/A

 

N/A

30

(13.6)

149

(67.6)

N/A

 

N/A

29

(13.2)

142

(64.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1010

 

N/A

 

N/A

60

(27.2)

154

(69.9)

N/A

 

N/A

57

(25.9)

147

(66.7)

Quiet-Line Condenser Models

 

 

 

 

 

 

 

 

 

 

 

63

 

N/A

39

(17.7)

 

N/A

21

(9.5)

N/A

37

(16.8)

 

N/A

20

(9.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

119

 

N/A

50

(22.7)

 

N/A

27 (12.3)

N/A

48

(21.8)

 

N/A

26 (11.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

127

 

N/A

76

(34.5)

 

N/A

38 (17.2)

N/A

72

(32.6)

 

N/A

36 (16.3)

 

 

 

 

 

 

 

 

 

 

 

 

143

 

N/A

126 (57.2)

 

N/A

64 (29.0)

N/A

120 (54.5)

 

N/A

61 (27.7)

 

 

 

 

 

 

 

 

 

 

 

 

214

 

N/A

161 (73.0)

 

N/A

81 (36.7)

N/A

153 (69.4)

 

N/A

77 (34.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

286

 

N/A

196 (88.9)

 

N/A

125

(56.7)

N/A

186 (84.4)

 

N/A

119

(54.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

409

 

N/A

 

N/A

 

N/A

129

(58.5)

N/A

 

N/A

 

N/A

125

(55.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

572

 

N/A

 

N/A

 

N/A

196

(88.9)

N/A

 

N/A

 

N/A

186

(84.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4

Interconnecting piping refrigerant charge

 

 

 

 

 

 

 

 

Line Size,

R-22, lb/100 ft. (kg/30m)

R-407C, lb/100 ft. (kg/30m)

 

 

 

 

 

 

O.D., in.

 

Liquid Line

Hot Gas Line

Liquid Line

Hot Gas Line

 

 

 

 

 

 

 

 

3/8

 

3.8

(1.7)

3.7

(1.7)

 

 

 

 

 

 

 

 

1/2

 

7.3

(3.3)

6.9

(3.1)

 

 

 

 

 

 

5/8

 

11.7 (5.3)

2.1 (1.0)

11.0 (5.0

2.2 (1.0)

 

 

 

 

 

 

3/4

 

16.6 (7.5)

3.0 (1.4)

15.7 (7.1)

3.1 (1.3)

 

 

 

 

 

 

 

 

7/8

 

24.4

(11.1)

4.4 (2.0)

23.0

(10.4)

4.5 (1.9)

 

 

 

 

 

 

 

 

1-1/8

 

41.4

(18.9)

7.8 (3.5)

39.3

(17.8)

7.8 (3.5)

 

 

 

 

 

 

 

1-3/8

 

63.3

(28.7)

11.8 (5.4)

59.8 (27.1

11.8 (5.4)

 

 

 

 

 

 

1-5/8

 

16.7 (7.6)

16.7 (7.6)

 

 

 

 

 

 

 

 

12

Image 16
Contents Liebert Air Cooled, Direct Drive Condensers Three-phase voltage is only voltage available as standard Example DCDF165-YOn condensers with VFD Control, Lee-temp receivers, Fan Speed Control 2-8 fan models onlyTable of Contents System Maintenance OperationProduct Description and Features Head Pressure Control TypesFan Speed Variable Frequency DriveSound Level Options Typical System ConfigurationsTransient Voltage Surge Suppression Option Fan Speed and VFD Lee-Temp DischargeDimensions and Weights Site ConsiderationsSee for typical condenser footprint dimensions 1067 mmFour-Fan41-3/16 Condenser 1046mm Condenser footprint dimensions Operation and component accessSee for typical Typical condenser footprint-dimensions Piping connections for 6- and 8-fan Fan Speed Condensers Site Preparation Condenser physical data Quiet-Line ModelsRefrigerant Planning Values R-407C refrigerant required, approximateReceiver Quiet-Line Condenser ModelsEquipment Inspection Packing MaterialHandling Unit on the Skid Unpacking the UnitRemoving the Skid and Attaching Slings Attaching legs to a 6-fan or 8-fan unit StepMounting the Condenser Attaching sling to a 6-fan or 8-fan unit for movingLine Voltage Wiring Electrical Supply Preparation60Hz condenser data 50Hz condenser full load amp valuesLow Voltage Control Wiring Low Voltage Monitoring Wiring-TCDV OnlyElectrical Connections Lee-Temp receiver electrical data, 50Hz and 60HzDelta-Connected Power Supply Wye-Connected Power SupplyVFD Control Condensers Tcdv only Disconnect EMC Filter for Delta-Connected Power Electric service connection and fuse block Electrical Field Connection DescriptionsElectrical field connections for VFD control condensers Inspection and Installation Refrigeration Piping Connections Piping GuidelinesField Piping Installation VFD and Fan Speed Control condenser pipingLee-Temp head pressure control condenser piping Single Circuit Shown General arrangement-Air cooled models with Lee-Temp controlSystem Dehydration/Leak Test and Charging Procedures Moving and Placing Equipment ElectricalPiping OtherStartup Checklist StartupGeneral Procedures System MaintenanceSpecial Procedures Condenser CleaningWhen to Clean How to CleanMaintenance Inspection Checklist Monthly Semiannually CondenserCondenser Electrical Panel Condenser Electric Panel Fan MotorsTroubleshooting Symptom Possible Cause Check or RemedySystem Maintenance System Maintenance Page Ne t ItiTi n That