Liebert 510 616 830, 205 251, 104 165 60Hz condenser data, 50Hz condenser full load amp values

Page 23

Inspection and Installation

Table 5

 

60Hz condenser data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model #

 

 

83, 104

 

 

165, 205

 

251, 308

 

415, 510

 

 

616

 

830, 1010

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

# of Fans

 

 

1

 

 

 

2

 

 

 

3

 

 

 

4

 

 

 

6

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

ph

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

Fan Speed Controlled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

 

 

4.8

 

6.0

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

1

 

2.5

 

3.1

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

 

 

1.9

 

2.4

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

 

 

 

 

8.3

 

9.5

 

15

11.8

13.0

 

15

15.3

16.5

 

20

23.6

24.8

25

30.6

31.8

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

3

 

 

 

4.2

 

4.8

 

15

5.9

6.5

 

15

7.6

8.2

 

15

11.8

12.4

15

15.2

15.8

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

 

 

 

 

3.3

 

3.8

 

15

4.7

5.2

 

15

6.1

6.6

 

15

9.4

9.9

15

12.2

12.7

15

VFD Controlled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

3

 

3.7

 

4.6

 

15

7.2

 

8.1

 

15

10.7

11.6

 

15

14.2

15.1

 

20

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

 

1.8

 

2.3

 

15

3.5

 

4.0

 

15

5.2

5.7

 

15

6.9

7.4

 

15

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

Lee-Temp Controlled/Fan-Cycling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

 

 

3.5

 

4.4

 

15

7.0

 

7.9

 

15

10.5

11.4

 

15

14.0

14.9

 

15

21.0

21.9

25

28.0

28.9

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

3

 

1.7

 

2.1

 

15

3.4

 

3.8

 

15

5.1

5.5

 

15

6.8

7.2

 

15

10.2

10.6

15

13.6

14.0

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

 

 

1.4

 

1.8

 

15

2.8

 

3.2

 

15

4.2

4.6

 

15

5.6

6.0

 

15

8.4

8.8

15

11.2

11.6

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

 

 

 

 

 

 

Table 6

60Hz condenser data, Quiet-Line (Lee-Temp controlled/fan-cycling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model #

ph

 

63

 

119, 127, 143

 

214

 

 

286

 

 

409

 

 

572

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

# of Fans

 

1

 

 

2

 

 

3

 

 

4

 

 

6

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

ph

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

FLA

WSA

OPD

208/230

 

1.8

2.3

15

3.6

4.1

15

5.4

5.9

15

7.2

7.7

15

10.8

11.3

15

14.4

14.9

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460

3

0.9

1.1

15

1.8

2.0

15

2.7

2.9

15

3.6

3.8

15

5.4

5.6

15

7.2

7.4

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

 

0.7

0.9

15

1.4

1.6

15

2.1

2.3

15

2.8

3.0

15

4.2

4.4

15

5.6

5.8

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

Table 7

50Hz condenser full load amp values

 

 

 

 

 

 

 

 

Condenser

Fan Speed

VFD

 

Lee Temp

Quiet-Line (Lee Temp

Control Type

Controlled

Controlled

Controlled/Fan-Cycling

Controlled/Fan-Cycling)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

Input

 

 

Input

 

 

Input

Model

# of

Voltage - Phase

Voltage - Phase

Voltage - Phase

Model

Voltage - Phase

 

 

 

 

 

 

 

 

 

 

 

 

#

Fans

200/230-1

380/415-3

200/230-3

380/415-3

200/230-3

380/415-3

#

200/230-3

380/415-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

83, 104

1

4.0

 

-

3.7

 

1.8

3.5

 

1.7

63

1.8

 

0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

119,

 

 

 

165, 205

2

 

3.7

7.2

 

3.5

7.0

 

3.4

127,

3.6

 

1.8

 

 

 

 

 

 

 

 

 

 

 

143

 

 

 

251, 308

3

 

5.4

10.7

 

5.2

10.5

 

5.1

214

5.4

 

2.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415, 510

4

 

7.1

14.2

 

6.9

14.0

 

6.8

286

7.2

 

3.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

616

6

 

10.8

 

21.0

 

10.2

409

10.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

830, 1010

8

 

14.2

 

28.0

 

13.6

572

14.4

 

7.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

Image 23
Contents Liebert Air Cooled, Direct Drive Condensers Fan Speed Control 2-8 fan models only Three-phase voltage is only voltage available as standardExample DCDF165-Y On condensers with VFD Control, Lee-temp receivers,Table of Contents Operation System MaintenanceVariable Frequency Drive Product Description and FeaturesHead Pressure Control Types Fan SpeedTransient Voltage Surge Suppression Option Typical System ConfigurationsSound Level Options Lee-Temp Discharge Fan Speed and VFDSite Considerations Dimensions and Weights1067 mm See for typical condenser footprint dimensionsFour-Fan41-3/16 Condenser 1046mm See for typical Operation and component accessCondenser footprint dimensions Typical condenser footprint-dimensions Piping connections for 6- and 8-fan Fan Speed Condensers Site Preparation Quiet-Line Models Condenser physical dataQuiet-Line Condenser Models Refrigerant Planning ValuesR-407C refrigerant required, approximate ReceiverPacking Material Equipment InspectionUnpacking the Unit Handling Unit on the SkidRemoving the Skid and Attaching Slings Step Attaching legs to a 6-fan or 8-fan unitAttaching sling to a 6-fan or 8-fan unit for moving Mounting the CondenserElectrical Supply Preparation Line Voltage Wiring50Hz condenser full load amp values 60Hz condenser dataLee-Temp receiver electrical data, 50Hz and 60Hz Low Voltage Control WiringLow Voltage Monitoring Wiring-TCDV Only Electrical ConnectionsVFD Control Condensers Tcdv only Wye-Connected Power SupplyDelta-Connected Power Supply Disconnect EMC Filter for Delta-Connected Power Electrical Field Connection Descriptions Electric service connection and fuse blockElectrical field connections for VFD control condensers Inspection and Installation Piping Guidelines Refrigeration Piping ConnectionsVFD and Fan Speed Control condenser piping Field Piping InstallationLee-Temp head pressure control condenser piping General arrangement-Air cooled models with Lee-Temp control Single Circuit ShownSystem Dehydration/Leak Test and Charging Procedures Other Moving and Placing EquipmentElectrical PipingStartup Startup ChecklistSystem Maintenance General ProceduresHow to Clean Special ProceduresCondenser Cleaning When to CleanFan Motors Maintenance Inspection ChecklistMonthly Semiannually Condenser Condenser Electrical Panel Condenser Electric PanelSymptom Possible Cause Check or Remedy TroubleshootingSystem Maintenance System Maintenance Page That Ne tIti Ti n