Liebert 205 251, 83, 104 165, 308 415 VFD Control Condensers Tcdv only, Wye-Connected Power Supply

Page 25

Inspection and Installation

3.7.1VFD Control Condensers (TCDV) only

The installer/startup technician must determine the type of 3-phase supply power being used for the VFD Control Condenser: Wye-connected power or Delta- connected power.

Wye-connected power has two different voltages that can be measured: Phase-to-Phase voltage (this is equal to the nominal input voltage) and Phase-to-Neutral voltage (typically used for small single phase loads (120 VAC or 277 VAC). See Figure 16.

Delta-connected power only has one voltage level that can be measured: Phase-to-Phase. See Figure 17.

3.7.2Wye-Connected Power Supply

No control changes are required if the Liebert VFD Control Condenser will be operated with Wye-con- nected power.

Figure 16 Wye-connected power diagram

 

Phase A

Winding

Phase B

B

 

Winding

A

Neutral

Winding

C Phase C

3.7.3Delta-Connected Power Supply

Figure 17 Delta-connected power diagram

Phase A

Winding

WindingA-B

C-A

Phase B

Winding B-C

Phase C

21

Image 25
Contents Liebert Air Cooled, Direct Drive Condensers Example DCDF165-Y Three-phase voltage is only voltage available as standardOn condensers with VFD Control, Lee-temp receivers, Fan Speed Control 2-8 fan models onlyTable of Contents Operation System MaintenanceHead Pressure Control Types Product Description and FeaturesFan Speed Variable Frequency DriveSound Level Options Typical System ConfigurationsTransient Voltage Surge Suppression Option Lee-Temp Discharge Fan Speed and VFDSite Considerations Dimensions and Weights1067 mm See for typical condenser footprint dimensionsFour-Fan41-3/16 Condenser 1046mm Condenser footprint dimensions Operation and component accessSee for typical Typical condenser footprint-dimensions Piping connections for 6- and 8-fan Fan Speed Condensers Site Preparation Quiet-Line Models Condenser physical dataR-407C refrigerant required, approximate Refrigerant Planning ValuesReceiver Quiet-Line Condenser ModelsPacking Material Equipment InspectionUnpacking the Unit Handling Unit on the SkidRemoving the Skid and Attaching Slings Step Attaching legs to a 6-fan or 8-fan unitAttaching sling to a 6-fan or 8-fan unit for moving Mounting the CondenserElectrical Supply Preparation Line Voltage Wiring50Hz condenser full load amp values 60Hz condenser dataLow Voltage Monitoring Wiring-TCDV Only Low Voltage Control WiringElectrical Connections Lee-Temp receiver electrical data, 50Hz and 60HzDelta-Connected Power Supply Wye-Connected Power SupplyVFD Control Condensers Tcdv only Disconnect EMC Filter for Delta-Connected Power Electrical Field Connection Descriptions Electric service connection and fuse blockElectrical field connections for VFD control condensers Inspection and Installation Piping Guidelines Refrigeration Piping ConnectionsVFD and Fan Speed Control condenser piping Field Piping InstallationLee-Temp head pressure control condenser piping General arrangement-Air cooled models with Lee-Temp control Single Circuit ShownSystem Dehydration/Leak Test and Charging Procedures Electrical Moving and Placing EquipmentPiping OtherStartup Startup ChecklistSystem Maintenance General ProceduresCondenser Cleaning Special ProceduresWhen to Clean How to CleanMonthly Semiannually Condenser Maintenance Inspection ChecklistCondenser Electrical Panel Condenser Electric Panel Fan MotorsSymptom Possible Cause Check or Remedy TroubleshootingSystem Maintenance System Maintenance Page Iti Ne tTi n That