Liebert 104 165, 83, 205 251, 308 415, 1010 manual Disconnect EMC Filter for Delta-Connected Power

Page 26

Inspection and Installation

Disconnect EMC Filter for Delta-Connected Power

Installer/startup technician needs to disconnect the EMC filter on the VFD to ensure proper operation if the Liebert VFD Control Condenser will be operated with Delta-connected power.

1.Disconnect the power supply before working on the unit.

2.Open the electrical panel cover and locate the VFD (Refer to Figure 20).

3.Using Figure 18, locate the small black plastic tab immediately to the right of the wiring connection block of the VFD control

4.Pull the tab to fully extend it, disconnecting the EMC filter from the circuit.

Figure 18 Disconnecting EMC filter for operation with Delta-connected power

A

Internal

EMC filter

Tab fully inserted:

EMC filter fitted

B

Internal

EMC filter

Tab fully extended:

EMC filter disconnected

22

Image 26
Contents Liebert Air Cooled, Direct Drive Condensers On condensers with VFD Control, Lee-temp receivers, Three-phase voltage is only voltage available as standardExample DCDF165-Y Fan Speed Control 2-8 fan models onlyTable of Contents System Maintenance OperationFan Speed Product Description and FeaturesHead Pressure Control Types Variable Frequency DriveTransient Voltage Surge Suppression Option Typical System ConfigurationsSound Level Options Fan Speed and VFD Lee-Temp DischargeDimensions and Weights Site ConsiderationsSee for typical condenser footprint dimensions 1067 mmFour-Fan41-3/16 Condenser 1046mm See for typical Operation and component accessCondenser footprint dimensions Typical condenser footprint-dimensions Piping connections for 6- and 8-fan Fan Speed Condensers Site Preparation Condenser physical data Quiet-Line ModelsReceiver Refrigerant Planning ValuesR-407C refrigerant required, approximate Quiet-Line Condenser ModelsEquipment Inspection Packing MaterialHandling Unit on the Skid Unpacking the UnitRemoving the Skid and Attaching Slings Attaching legs to a 6-fan or 8-fan unit StepMounting the Condenser Attaching sling to a 6-fan or 8-fan unit for movingLine Voltage Wiring Electrical Supply Preparation60Hz condenser data 50Hz condenser full load amp valuesElectrical Connections Low Voltage Control WiringLow Voltage Monitoring Wiring-TCDV Only Lee-Temp receiver electrical data, 50Hz and 60HzVFD Control Condensers Tcdv only Wye-Connected Power SupplyDelta-Connected Power Supply Disconnect EMC Filter for Delta-Connected Power Electric service connection and fuse block Electrical Field Connection DescriptionsElectrical field connections for VFD control condensers Inspection and Installation Refrigeration Piping Connections Piping GuidelinesField Piping Installation VFD and Fan Speed Control condenser pipingLee-Temp head pressure control condenser piping Single Circuit Shown General arrangement-Air cooled models with Lee-Temp controlSystem Dehydration/Leak Test and Charging Procedures Piping Moving and Placing EquipmentElectrical OtherStartup Checklist StartupGeneral Procedures System MaintenanceWhen to Clean Special ProceduresCondenser Cleaning How to CleanCondenser Electrical Panel Condenser Electric Panel Maintenance Inspection ChecklistMonthly Semiannually Condenser Fan MotorsTroubleshooting Symptom Possible Cause Check or RemedySystem Maintenance System Maintenance Page Ti n Ne tIti That