| System Maintenance |
| Table 9 | Troubleshooting |
| |
|
|
|
|
|
| Symptom |
| Possible Cause | Check or Remedy |
|
|
| No power to condenser | Check voltage at input terminal block |
|
|
|
|
|
| Condenser will not start | Circuit breaker for low voltage | Locate problem in condenser electrical | |
| transformer in condenser is tripped | panel and repair | ||
|
|
| ||
|
|
| No low voltage signal to/from indoor unit | Locate open circuit and repair |
|
|
|
|
|
| Low indoor unit | Insufficient refrigerant in system | Check for leaks, repair, and add refrigerant | |
|
|
| ||
| Check schematic for recommended | |||
| suction pressure | |||
|
|
| setpoints too low | setpoints and adjust. |
| Low discharge pressure | Faulty head pressure control valve | Replace if defective | |
| or condenser FSC/VFD control | |||
|
|
|
| |
|
|
| Dirty condenser fins | Clean coil |
|
|
|
|
|
|
|
|
| Check for low voltage signal from indoor unit |
|
|
|
|
|
| High discharge pressure | Condenser fans not operating | Check fan motors and fuses | |
|
| |||
|
|
|
| Check for correct ambient thermostat |
|
|
|
| setpoints, as applicable. |
|
|
| High refrigerant charge | Check refrigerant charge |
|
|
|
| |
| VFD Condenser trips out |
|
| |
| on overvoltage | Supply voltage is Delta configuration | Shut off AC voltage, locate the VFD, pull out | |
| (OU displayed on VFD | or is ungrounded/high impedance | the EMC tab and reconnect power | |
| controller) |
|
|
|
|
|
| No voltage or improper phasing exists | Check voltage at input terminal block |
|
|
| at condenser | |
| TVSS indicator lights are |
| ||
| Electrical connections to TVSS are |
| ||
| extinguished or red LED is | Locate connection problem and repair | ||
| faulty | |||
| illuminated and monitoring |
| ||
|
|
| ||
| terminals 11/12 are closed | A surge exceeding the rating | Replace TVSS and inspect other | |
|
|
| components for damage and replace them if | |
|
|
| of the TVSS has occurred | |
|
|
| necessary | |
|
|
|
| |
|
|
|
|
|
36