American Dryer Corp MDG-50 installation manual Multiple Dryer Common Venting

Page 19

MULTIPLE DRYER (Common) VENTING

If it is not feasible to provide separate exhaust ducts for each dryer, ducts for individual dryers may be channeled into a common main duct. Each dryer is provided with a back draft damper. The individual ducts should enter the bottom or side of the main duct at an angle not more than 45° in the direction of the airflow.

The main common duct may be any shape so long as the minimum cross-sectional area is provided. The main duct should be tapered with the diameter increasing before each individual 8-inch duct is added (refer to Illus. C for horizontal venting and Illus D for vertical venting).

IMPORTANT: No more than four (4) dryers maximum should be connected to one (1) main common duct with a vertical run.

NOTE: Distance between dryer single ducts being connected to the main common duct must be a minimum of 34-1/4" (dryer width).

Duct work should be laid out in such a manner where allowances are made at rear area of the dryer for removal of rear service panels or guards.

The illustrations on page 16 show the minimum cross-section area for multiple dryer venting. These figures must be increased in proportion if the main duct run from the last dryer to where it exhausts has numerous elbows or is unusually long.

IMPORTANT: For extended duct work runs, the cross-section area of the duct can only be increased to an extent. For extended duct work runs, a professional HVAC firm should be consulted for proper venting information.

Refer to page 16 for multiple dryer horizontal venting and vertical venting examples and illustrations.

15

Image 19
Contents MDG-50 Installation Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Routine Maintenance Important Information SectionPersonal Injury or Fire could Result Safety PrecautionsPage Specifications SpecificationsSpecifications Unpacking and Setting UP Installation ProceduresLocation Requirements Dryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Single Dryer Venting Illus. B Multiple Dryer Common Venting ILLUS. D Importantventingreminders Electrical Requirements Electrical InformationMust be Provided Odfn Klwh Uhhq Important a Circuit Serving Each Dryer Must be Provided DG-50 GAS Injury and Improper Operation of the Dryer GAS InformationType of GAS Page Page Preparation for Operation and START-UP Preoperational Tests Preoperational Instructions Page OPL Models Shut Down Instructions Parts ServiceSection Returning Warranty CardsCleaning Routine MaintenanceLubrication AdjustmentsNo L.E.D. light emitting diode display TroubleshootingDrive motor not operating does not start Blower motor not operating does not start Microprocessor controller computer display reads door Microprocessor computer display reads dSFLNo heat, ignitor sparks, burner goes on and off right away Dryer operates but is taking too long to dry Dryer or scraping noise at basket tumbler area Condensation on main door glassMain burners are burning with a yellow flame Excessive noise or vibrationDrive motor only not operating Blower motor only not operating Heating unit not operating ALL temperature selectionsDryer operates but is taking too long to dry load Dryer is cycling on hi-limit thermostat Data Label Technical InformationSerial Number Timing Legend Reversing Timer SPIN/DWELL AdjustmentsProcedure for Functional Check Replacement Components Direct Spark Ignition DSI System 10/30/00-150