3 Operating the SAMMS-MV Device
2.The UP, DOWN, and ENTER keys are disabled for this function.
3.Press the (F)unction key to go to other functions.
F26 - Baud Rate
1.Press the LIST key to view the active setting. Allowable settings are 2400, 4800, or 9600 baud. The factory default is 4800.
2.To change the setting, you must be in program mode.
3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.
4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the
5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.
6.Press the (F)unction key to step through to another function.
F27 - Address
1.Press the LIST key to view the active setting. Allowable addresses are
2.To change the setting, you must be in program mode.
3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.
4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the
5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.
6.Press the (F)unction key to step through to another function.
39