Siemens SAMMS-MV user manual F26 Baud Rate, F27 Address

Page 41

3 Operating the SAMMS-MV Device

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F26 - Baud Rate

1.Press the LIST key to view the active setting. Allowable settings are 2400, 4800, or 9600 baud. The factory default is 4800.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F27 - Address

1.Press the LIST key to view the active setting. Allowable addresses are 1-224. The factory default is 200.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

39

Image 41
Contents SAMMS-MV Qualified Person Contents Qualified Person Signal WordsField Service Operation About this Manual Advanced Protection for Medium-Voltage Motors SAMMS-MV Device ModelsProgramming Control Circuits Using the Standardized Control PanelOverload Protection SAMMS-MV Model Change settings requires password Yes Remote inputs OneOutputs One Light barsInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Using the Reset/Test Push Button Password ProtectionPerforming a Lamp Test Performing an Overload Relay TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Motor Ambient Temperature Ridethrough Upon Loss of Power SAMMS-MVX OnlyIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-MVX OnlyODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Phase Unbalance Ultimate Trip Level and Service FactorDual Overload Protection SAMMS-MVX Only Jam Protection SAMMS-MVX OnlyRepetitive Starts Ground Fault DetectionStart Inhibit Cooling Time Constants12 Multi-start scenario for an ODP motor Using the Hand Held Communicator HHC Autoreset After a Trip SAMMS-MVX OnlyEmergency Restarting Function KeyFunction Number 5A CT primary current low speed if used Service factor5A CT primary current if used Full load current for OLR No Motor type Overload trip class class 2 throughUP and Down Keys Using the Enter KeyUsing the SAMMS-MV Device Func- tions ON/OFF Default Value Select ground fault pick-up currentMeans warning Select jam pickup current 120-400% Iflc F24 Loss of Load13 Entering and changing passwords F0 Ambient Temperature Program Mode/PasswordsSAMMS-MV Functions F1 Control Circuit Number and Incomplete Se- quence StatusF3 Size for Overload Relay #2 SAMMS-MVX Only Overload Setting Step Default Relay Size RangeF4 Full-Load Current for Overload Relay #1 18 to 72AF6A Motor Type F6 Service FactorF7 Overload Trip Class F7A Cold Stall TimeF9 Phase Unbalance Protection F8 Autoreset SAMMS-MVX OnlyF10 Display Time to Restart F11 Emergency RestartingF12A Ground Fault Pickup Current F12 Ground Fault Protection or WarningSize Pickup Current Default H3A-H3C 7A-I FLC 10A 20A F13 Set Programmable Timer #1F16 Trip Current F21 Reset Motor DataF17 Current Unbalance F18 Display Total Elapsed Run Time of the MotorF22 Process Current Warning Level SAMMS-MVX Only F25 Percentage of Motor Winding TemperatureF23 Jam Protection SAMMS-MVX Only F23A Jam Pickup Current SAMMS-MVX OnlyF27 Address F26 Baud RateTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc