Siemens SAMMS-MV user manual F16 Trip Current, F17 Current Unbalance, F19 Number of Motor Starts

Page 39

3 Operating the SAMMS-MV Device

a. Because only four characters can display at a time, individual line currents of 1000 amps and above are displayed as three dashes following the phase designa- tor, e.g., A - - -.

b. For sizes H3A, H3B, and H3C, the current is displayed to the nearest 1 amp. For size H6, currents are displayed to the nearest 2 amps.

2.To view another line current, press the UP or DOWN key to scroll through the four selections.

3.The ENTER key is disabled for this function.

4.Press the (F)unction key to go to other functions.

F16 - Trip Current

1.Press the LIST key to view the value of the current that caused the most recent trip.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F17 - Current Unbalance

1.Press the LIST key to view the percentage current unbal- ance. When unbalance protection is disabled (F9 = OFF), OFF is displayed. The percentage unbalance is the ratio of the greatest deviation of the three phase currents from their average to the average of the three phase currents ex- pressed as a percentage.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F18 - Display Total Elapsed Run Time of the Motor

1.Press the LIST key to view the total elapsed running time of the motor. The run time is displayed in tens of hours as follows:

Actual Number of Hours

Displayed Time

 

 

0

0.0

 

 

9999

999.9

 

 

10000

1000

 

 

65535

6553

 

 

65536

0.0 (roll over)

 

 

The displayed value does not increment until a full hour, or for elapsed times greater than 10000 hours a full ten hours, have elapsed. Internally, however, the elapsed time is maintained to the nearest 0.1 second.

Note: The value can be reset to zero with F21.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F19 - Number of Motor Starts

1.Press the LIST key to view the number of motor starts. The number of starts is displayed in tens of starts as follows:

Actual Number of Starts

Displayed Number

 

 

0

0.0

 

 

9999

999.9

 

 

10000

1000

 

 

65535

6553

 

 

65536

0.0 (roll over)

Note: The value can be reset to zero with F21.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F20 - Number of Overload Trips

1.Press the LIST key to view the number of overload trips, up to 9999.

Note: The value can be reset to zero with F21.

2.The UP, DOWN, and ENTER keys are disabled for this function.

3.Press the (F)unction key to go to other functions.

F21 - Reset Motor Data

1.To reset to zero the elapsed running time, the number of starts, and the number of overload trips, press the LIST key. “CLr” is displayed.

2.Press the ENTER key. “SUrE” is displayed.

3.Press the ENTER key again to zero the motor data.

4.To return to Step 1, press the LIST key at any time.

5.The UP and DOWN keys are disabled for this function.

6.Press the (F)unction key to go to other functions.

37

Image 39
Contents SAMMS-MV Qualified Person Contents Signal Words Field Service OperationQualified Person About this Manual Advanced Protection for Medium-Voltage Motors SAMMS-MV Device ModelsUsing the Standardized Control Panel Overload ProtectionProgramming Control Circuits Light bars Change settings requires password Yes Remote inputs OneSAMMS-MV Model Outputs OneInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Performing an Overload Relay Test Password ProtectionUsing the Reset/Test Push Button Performing a Lamp TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Intelligent Reduced-Voltage Starting SAMMS-MVX Only Ridethrough Upon Loss of Power SAMMS-MVX OnlyMotor Ambient Temperature Incomplete SequenceODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Jam Protection SAMMS-MVX Only Ultimate Trip Level and Service FactorPhase Unbalance Dual Overload Protection SAMMS-MVX OnlyCooling Time Constants Ground Fault DetectionRepetitive Starts Start Inhibit12 Multi-start scenario for an ODP motor Function Key Autoreset After a Trip SAMMS-MVX OnlyUsing the Hand Held Communicator HHC Emergency RestartingMotor type Overload trip class class 2 through 5A CT primary current low speed if used Service factorFunction Number 5A CT primary current if used Full load current for OLR NoUsing the Enter Key Using the SAMMS-MV Device Func- tionsUP and Down Keys ON/OFF Select jam pickup current 120-400% Iflc F24 Loss of Load Select ground fault pick-up currentDefault Value Means warning13 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status Program Mode/PasswordsF0 Ambient Temperature SAMMS-MV Functions18 to 72A Overload Setting Step Default Relay Size RangeF3 Size for Overload Relay #2 SAMMS-MVX Only F4 Full-Load Current for Overload Relay #1F7A Cold Stall Time F6 Service FactorF6A Motor Type F7 Overload Trip ClassF11 Emergency Restarting F8 Autoreset SAMMS-MVX OnlyF9 Phase Unbalance Protection F10 Display Time to RestartF13 Set Programmable Timer #1 F12 Ground Fault Protection or WarningF12A Ground Fault Pickup Current Size Pickup Current Default H3A-H3C 7A-I FLC 10A 20AF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF16 Trip Current F17 Current UnbalanceF23A Jam Pickup Current SAMMS-MVX Only F25 Percentage of Motor Winding TemperatureF22 Process Current Warning Level SAMMS-MVX Only F23 Jam Protection SAMMS-MVX OnlyF27 Address F26 Baud RateTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc