Siemens user manual F3 Size for Overload Relay #2 SAMMS-MVX Only, 18 to 72A, 60 to 240A

Page 35

3 Operating the SAMMS-MV Device

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

F3 - Size for Overload Relay #2 (SAMMS-MVX Only)

Overload relay #2 protects two-speed motors running on low speed. The possible values are H3A, H3B, H3C, H6 and OFF. OFF appears for single-speed motors. Use the following proce- dure to display the size for overload relay #2.

1.Press the LIST key to view the size selected for overload relay #2.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

F4 - Full-Load Current for Overload Relay #1

1.Press the LIST key to view the active full-load current setting for overload relay #1. The setting should normally be the full load current as shown on the motor nameplate (high speed for two-speed machine). The range of possible settings and the factory default value depend on the size displayed in F2 as follows:

Overload

Setting

Step

Default

Relay Size

Range

 

 

 

 

 

 

H3A

18 to 72A

1A

18

 

 

 

 

H3B

60 to 240A

1A

60

 

 

 

 

H3C

192 to 400A

1A

192

 

 

 

 

H6

320 to 720A

2A

320

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-MV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4).

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F4A - 5A CT Primary Current Selection for Overload Relay #1

SAMMS-MV is normally used with SAMMS sensors to provide the current input signals to the device. Optionally, SAMMS-MV may be used with conventional 5A secondary current trans- formers.

1.Press the LIST key to view the sensor in use for overload relay #1. If standard SAMMS sensors are used, the display will read “OFF.” If 5A secondary CT’s are in use, the CT primary current will be displayed.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F5 - Full-Load Current for Overload Relay #2 (SAMMS-MVX Only)

1.Press the LIST key to view the active full-load current setting for overload relay #2. This setting should normally be the full load current for the low speed shown on the motor name- plate. The range of possible settings and the factory default value depend on the size displayed in F3. The values are similar to those found in the table in the procedure for F4. If the control is not a two-speed control, OFF appears on the display, and UP, DOWN and ENTER keys become disabled.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-MV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4).

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F5A - 5A CT Primary Current Selection for Overload Relay #2 (SAMMS-MVX Only)

SAMMS-MV is normally used with SAMMS sensors to provide the current input signals to the device. Optionally, SAMMS-MV may be used with conventional 5A secondary current trans- formers.

33

Image 35
Contents SAMMS-MV Qualified Person Contents Qualified Person Signal WordsField Service Operation About this Manual Advanced Protection for Medium-Voltage Motors SAMMS-MV Device ModelsProgramming Control Circuits Using the Standardized Control PanelOverload Protection Light bars Change settings requires password Yes Remote inputs OneSAMMS-MV Model Outputs OneInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Performing an Overload Relay Test Password ProtectionUsing the Reset/Test Push Button Performing a Lamp TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Intelligent Reduced-Voltage Starting SAMMS-MVX Only Ridethrough Upon Loss of Power SAMMS-MVX OnlyMotor Ambient Temperature Incomplete SequenceODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Jam Protection SAMMS-MVX Only Ultimate Trip Level and Service FactorPhase Unbalance Dual Overload Protection SAMMS-MVX OnlyCooling Time Constants Ground Fault DetectionRepetitive Starts Start Inhibit12 Multi-start scenario for an ODP motor Function Key Autoreset After a Trip SAMMS-MVX OnlyUsing the Hand Held Communicator HHC Emergency RestartingMotor type Overload trip class class 2 through 5A CT primary current low speed if used Service factorFunction Number 5A CT primary current if used Full load current for OLR NoUP and Down Keys Using the Enter KeyUsing the SAMMS-MV Device Func- tions ON/OFF Select jam pickup current 120-400% Iflc F24 Loss of Load Select ground fault pick-up currentDefault Value Means warning13 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status Program Mode/PasswordsF0 Ambient Temperature SAMMS-MV Functions18 to 72A Overload Setting Step Default Relay Size RangeF3 Size for Overload Relay #2 SAMMS-MVX Only F4 Full-Load Current for Overload Relay #1F7A Cold Stall Time F6 Service FactorF6A Motor Type F7 Overload Trip ClassF11 Emergency Restarting F8 Autoreset SAMMS-MVX OnlyF9 Phase Unbalance Protection F10 Display Time to RestartF13 Set Programmable Timer #1 F12 Ground Fault Protection or WarningF12A Ground Fault Pickup Current Size Pickup Current Default H3A-H3C 7A-I FLC 10A 20AF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF16 Trip Current F17 Current UnbalanceF23A Jam Pickup Current SAMMS-MVX Only F25 Percentage of Motor Winding TemperatureF22 Process Current Warning Level SAMMS-MVX Only F23 Jam Protection SAMMS-MVX OnlyF27 Address F26 Baud RateTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc