Siemens SAMMS-MV F6 Service Factor, F6A Motor Type, F7 Overload Trip Class, F7A Cold Stall Time

Page 36

3 Operating the SAMMS-MV Device

1.Press the LIST key to view the sensor in use for overload relay #2. If standard SAMMS sensors are used, the display will read “OFF.” If 5A secondary CT’s are in use, the CT primary current will be displayed.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F6 - Service Factor

1.Press the LIST key to view the active service factor, 1.0 or 1.15. The factory default is 1.15. A service factor of 1.15 adjusts the overload trip thresholds up by 15% over their values for a service factor of 1.0. This results in more margin before tripping.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to alternate between the two choices until the selected value is displayed.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-MV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4.)

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F6A - Motor Type

1.Press the LIST key to view the motor type in use. The factory default is “OdP” for open drip proof. “EFC” designates totally enclosed fan cooled.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to alternate between the two choices until the selected value is displayed.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-MV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4.)

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.”Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F7 - Overload Trip Class

The trip class is the time in seconds that it takes the overload relay to trip for a starting current of 600% of the full-load current setting. The range of possible values is 2-23.

1.Press the LIST key to view the active trip class.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-MV device stores the new setting. (If you make an incorrect selection, repeat steps 3 and 4.)

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.”Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F7A - Cold Stall Time

1.Press the LIST key to view the active cold stall time in use. (The range of possible values is between 5 and 100 seconds in increments of one second. The factory default value is 10 seconds. If the cold stall time is more than 100 seconds, enter 100.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key to scroll through the range of settings until the selected setting appears.

4.Press the ENTER key to change the active setting to the selected value. The display becomes blank while you hold down the ENTER key, and the SAMMS-MV device stores the new setting. If the overload class selected exceeds the cold stall time, the word “SUrE” appears on the display requiring reentry before accepting the data.

Important: The word “SUrE” is used as a reminder that supplemental protection is required if the motor acceleration time (overload class) exceeds the allowable stall time for the motor. A speed switch should be used as an input source to open the contactor if the switch senses a locked rotor or stall condition.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

34

Image 36
Contents SAMMS-MV Qualified Person Contents Signal Words Field Service OperationQualified Person About this Manual SAMMS-MV Device Models Advanced Protection for Medium-Voltage MotorsUsing the Standardized Control Panel Overload ProtectionProgramming Control Circuits Change settings requires password Yes Remote inputs One SAMMS-MV ModelOutputs One Light barsInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Password Protection Using the Reset/Test Push ButtonPerforming a Lamp Test Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Ridethrough Upon Loss of Power SAMMS-MVX Only Motor Ambient TemperatureIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-MVX OnlyODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Ultimate Trip Level and Service Factor Phase UnbalanceDual Overload Protection SAMMS-MVX Only Jam Protection SAMMS-MVX OnlyGround Fault Detection Repetitive StartsStart Inhibit Cooling Time Constants12 Multi-start scenario for an ODP motor Autoreset After a Trip SAMMS-MVX Only Using the Hand Held Communicator HHCEmergency Restarting Function Key5A CT primary current low speed if used Service factor Function Number5A CT primary current if used Full load current for OLR No Motor type Overload trip class class 2 throughUsing the Enter Key Using the SAMMS-MV Device Func- tionsUP and Down Keys ON/OFF Select ground fault pick-up current Default ValueMeans warning Select jam pickup current 120-400% Iflc F24 Loss of Load13 Entering and changing passwords Program Mode/Passwords F0 Ambient TemperatureSAMMS-MV Functions F1 Control Circuit Number and Incomplete Se- quence StatusOverload Setting Step Default Relay Size Range F3 Size for Overload Relay #2 SAMMS-MVX OnlyF4 Full-Load Current for Overload Relay #1 18 to 72AF6 Service Factor F6A Motor TypeF7 Overload Trip Class F7A Cold Stall TimeF8 Autoreset SAMMS-MVX Only F9 Phase Unbalance ProtectionF10 Display Time to Restart F11 Emergency RestartingF12 Ground Fault Protection or Warning F12A Ground Fault Pickup CurrentSize Pickup Current Default H3A-H3C 7A-I FLC 10A 20A F13 Set Programmable Timer #1F21 Reset Motor Data F16 Trip CurrentF17 Current Unbalance F18 Display Total Elapsed Run Time of the MotorF25 Percentage of Motor Winding Temperature F22 Process Current Warning Level SAMMS-MVX OnlyF23 Jam Protection SAMMS-MVX Only F23A Jam Pickup Current SAMMS-MVX OnlyF26 Baud Rate F27 AddressTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc