Siemens user manual Incomplete Sequence, Intelligent Reduced-Voltage Starting SAMMS-MVX Only

Page 19

3 Operating the SAMMS-MV Device

3.7 Incomplete Sequence

Sometimes the motor contactors do not respond in a timely manner to start, stop, transition, speed or direction change commands from the controller. If the SAMMS-MV device does not detect motor current one second after issuing a start command or if the SAMMS-MV device detects motor current one second after issuing a stop command, an Incomplete Sequence trip occurs. The motor contactors are opened and the Incomplete Sequence LED illuminates solidly. In standard reduced-voltage autotransformer (RVA) starters, an incomplete sequence also occurs if the remote RUN seal-in contact wired to pin 9 does not close within one second of the transition from starting to full-speed operation. This function can be disabled permanently when configured at the factory. You can also disable it with the Hand Held Communicator to the SAMMS-MV device. This is helpful when the controller is tested before connecting to the motor. After connecting the HHC, use the function UP and DOWN buttons to select F1. While pressing the ENTER button for a period of one second push START. Repeating the same process enables the incomplete sequence protection function.

3.8Intelligent Reduced-Voltage Starting (SAMMS-MVX Only)

Intelligent reduced-voltage starting is provided in all standard reduced-voltage Siemens starters. The advantage of this fea- ture is that the transition from reduced to full voltage is deter- mined by the magnitude of the actual motor current and not by a timer. This optimizes the transition.

When a motor with intelligent reduced-voltage starting is started, a 30 second timer is energized. If the timer times out, the transition to full voltage commences as a fail-safe measure. If, before the 30 second timer times out, the motor current drops to below the full-load current setting, the transition commences.

The state of the RUN contactor, whose auxiliary contact is connected to Remote input 4 (pin 9), is checked one second after the transition. If the contactor is not closed, an incomplete sequence trip occurs.

3.9Ridethrough Upon Loss of Power (SAMMS-MVX Only)

If a motor is running and control power is lost, the motor restarts automatically with two-wire control as soon as power is re- stored. With three-wire control, you must restart the motor manually. The optional ridethrough feature available with SAMMS-MVX allows three-wire controls to ride through power outages of up to one second. This feature is especially useful where the power system is subject to momentary interruptions. If, while the motor is running, power is lost to a three-wire control having the ridethrough option, the contactors are opened to prevent chattering and then reclosed automatically if power returns within one second.

3.10 Overload Protection

Medium-voltage motors are rotor limited under locked rotor conditions, and stator limited under running overload condi- tions. Additionally, the type of motor construction affects the thermal behavior of the rotor. For example, open drip-proof

motors have significantly shorter cold stall times than totally enclosed fan-cooled motors. The motor protection algorithm in the SAMMS-MV device is designed specifically to provide rotor protection based on the type of motor construction, and to differentiate between a stalled rotor and a rotor accelerating to running speed.

The motor overload protection function is based on calculating the motor’s winding, housing, and rotor temperatures. These temperatures are compared to the allowable temperature limits for the motor’s winding, housing, and rotor. On the basis of this comparison, the SAMMS-MV device either stops the motor or allows it to run.

For example, consider the motor winding and rotor temperature rises illustrated in Figure 3.5. The motor starts for 5 seconds and runs for a period of 2200 seconds. Then, the motor is subjected to a running overload condition that raises the winding tempera- ture to the maximum allowable winding temperature rise result- ing in an overload trip. At this temperature, the motor cannot start until the motor winding temperature cools down to the full- load temperature. The motor can then start and run at full-load current. Figure 3.6 depicts the temperature rise in the rotor and stator winding during a 10 second stall for an ODP motor. In this case, the rotor temperature rises at a rate faster than the winding temperature, and reaches the maximum allowable value resulting in a trip. In order to prevent damage to the motor, SAMMS-MV will not allow the motor to start until the winding and the rotor temperatures cool down to the full load tempera- ture or less.

In the motor model, the greatest of the root mean square (RMS) current values for the motor phases is converted into a heat-like quantity. This is done by a mathematical function that depends on the ratio of the RMS current to the full-load current set for the motor. The function is based not only on ideal overload characteristics, but also on empirical motor data. The heat-like quantity is analogous to an input source of current to the electric-circuit analog. The exact values of the various elements in the circuit depend, in some cases, on nameplate data entered for the particular motor being protected. Unlike the method of protection in conventional overload relays, the motor model is general enough to protect many classes of motors, yet sophisticated enough to offer customized protection to particu- lar motors. To customize protection to the motor enter the following nameplate data:

full-load current setting (F4)

service factor (F6)

type of motor construction (Open Drip Proof (ODP) or Totally Enclosed Fan Cooled (EFC) (F6)

cold stall time, if available (F7)

motor ambient temperature (F0)

3.11 Motor Ambient Temperature

Motors are used in a wide range of temperatures. However, motors designed according to NEMA standards are rated at 40°C ambient temperature.

The SAMMS-MV allows you to decrease or increase the motor’s thermal capacity according to the motor’s ambient

17

Image 19
Contents SAMMS-MV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual Advanced Protection for Medium-Voltage Motors SAMMS-MV Device ModelsOverload Protection Using the Standardized Control PanelProgramming Control Circuits Light bars Change settings requires password Yes Remote inputs OneSAMMS-MV Model Outputs OneInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Performing an Overload Relay Test Password ProtectionUsing the Reset/Test Push Button Performing a Lamp TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Intelligent Reduced-Voltage Starting SAMMS-MVX Only Ridethrough Upon Loss of Power SAMMS-MVX OnlyMotor Ambient Temperature Incomplete SequenceODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Jam Protection SAMMS-MVX Only Ultimate Trip Level and Service FactorPhase Unbalance Dual Overload Protection SAMMS-MVX OnlyCooling Time Constants Ground Fault DetectionRepetitive Starts Start Inhibit12 Multi-start scenario for an ODP motor Function Key Autoreset After a Trip SAMMS-MVX OnlyUsing the Hand Held Communicator HHC Emergency RestartingMotor type Overload trip class class 2 through 5A CT primary current low speed if used Service factorFunction Number 5A CT primary current if used Full load current for OLR NoUsing the SAMMS-MV Device Func- tions Using the Enter KeyUP and Down Keys ON/OFF Select jam pickup current 120-400% Iflc F24 Loss of Load Select ground fault pick-up currentDefault Value Means warning13 Entering and changing passwords F1 Control Circuit Number and Incomplete Se- quence Status Program Mode/PasswordsF0 Ambient Temperature SAMMS-MV Functions18 to 72A Overload Setting Step Default Relay Size RangeF3 Size for Overload Relay #2 SAMMS-MVX Only F4 Full-Load Current for Overload Relay #1F7A Cold Stall Time F6 Service FactorF6A Motor Type F7 Overload Trip ClassF11 Emergency Restarting F8 Autoreset SAMMS-MVX OnlyF9 Phase Unbalance Protection F10 Display Time to RestartF13 Set Programmable Timer #1 F12 Ground Fault Protection or WarningF12A Ground Fault Pickup Current Size Pickup Current Default H3A-H3C 7A-I FLC 10A 20AF18 Display Total Elapsed Run Time of the Motor F21 Reset Motor DataF16 Trip Current F17 Current UnbalanceF23A Jam Pickup Current SAMMS-MVX Only F25 Percentage of Motor Winding TemperatureF22 Process Current Warning Level SAMMS-MVX Only F23 Jam Protection SAMMS-MVX OnlyF27 Address F26 Baud RateTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc