Siemens user manual Program Mode/Passwords, SAMMS-MV Functions, F0 Ambient Temperature

Page 34

3 Operating the SAMMS-MV Device

3.29.1 Program Mode/Passwords

To access the functions in program mode, the user is required to enter a password. The default password is “0000,” and may be changed at any time. To enter the password and have access to program mode:

1.Press and hold the (F)unction key for several seconds until “dISP” is displayed.

2.Press the UP or DOWN key to change to the program mode. The display reads “Prog.”

3.Press the ENTER key, and the display shows “HHH0,” the prompt for entering the password.

4.Press the UP or DOWN key to select the first digit, then press ENTER. The display reads “HH0-.”

5.Continue to select password digits and press ENTER to enter each digit.

6.After correctly entering the four digit password, the display reads “- - - -,” and pressing ENTER gives access to the functions in program mode.

7.If the password was entered incorrectly, the display will read “Err.” Press the ENTER key to return to program mode and try again.

To change the password:

1.Enter the password as described above.

2.With the password entered and the display showing “- - - -,” press the UP or DOWN key to enter change mode. The display reads “CHg.”

3.Press the ENTER key, and the display shows “HHH0,” the prompt for entering the new password.

4.Enter the new password in the same way described above. After entering all four digits of the new password, the display will again display “HHH0.”

5.Enter the new password a second time. If it was entered correctly the display reads “donE,” and pressing ENTER gives access to the functions in program mode.

6.If the password was entered incorrectly, the display will read “Err.” Press the ENTER key to return to program mode and try again.

3.29.2 SAMMS-MV Functions

F0 - Ambient Temperature

1.Press the LIST key to view the ambient temperature se- lected. The default value is 40° C and the range of possible values is from 0° C to 70° C in increments of 5° C.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

F1 - Control Circuit Number and Incomplete Se- quence Status

1.Press the LIST key to view the control circuit number programmed at the factory. The circuit numbers range from 0 through 9999. (The UP, DOWN and ENTER keys become disabled.)

2.For SAMMS-MVE, to change the settings, you must be in the program mode. The available selections are program blocks 10-16 (refer to table 3.3). If you have loaded a custom circuit, the designation for that circuit will be shown.

3.Press the UP or DOWN key to scroll through the range of circuit numbers, until the desired circuit number appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

7.To enable or disable incomplete sequence, press the EN- TER key for a period of one second or more. A “.” will be displayed after the F1 on the HHC if incomplete sequence is enabled. (The SAMMS-MV is shipped from the factory with the incomplete sequence enabled.)

F2 - Size for Overload Relay #1

Overload relay #1 protects single-speed motors and two- speed motors running on high speed. The possible values are H3A, H3B, H3C and H6. Use the following procedure to display the size for overload relay #1.

1.Press the LIST key to view the size selected for overload relay #1.

2.To change the setting, you must be in program mode.

3.Press the UP or DOWN key to scroll through the range of settings, until the selected setting appears on the display.

4.Press the ENTER key to change the active setting to the selected setting. The display becomes blank while you hold down the ENTER key and the SAMMS-MV device stores the new setting.

32

Image 34
Contents SAMMS-MV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual SAMMS-MV Device Models Advanced Protection for Medium-Voltage MotorsOverload Protection Using the Standardized Control PanelProgramming Control Circuits Outputs One Change settings requires password Yes Remote inputs OneSAMMS-MV Model Light barsInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Performing a Lamp Test Password ProtectionUsing the Reset/Test Push Button Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Incomplete Sequence Ridethrough Upon Loss of Power SAMMS-MVX OnlyMotor Ambient Temperature Intelligent Reduced-Voltage Starting SAMMS-MVX OnlyODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Dual Overload Protection SAMMS-MVX Only Ultimate Trip Level and Service FactorPhase Unbalance Jam Protection SAMMS-MVX OnlyStart Inhibit Ground Fault DetectionRepetitive Starts Cooling Time Constants12 Multi-start scenario for an ODP motor Emergency Restarting Autoreset After a Trip SAMMS-MVX OnlyUsing the Hand Held Communicator HHC Function Key5A CT primary current if used Full load current for OLR No 5A CT primary current low speed if used Service factorFunction Number Motor type Overload trip class class 2 throughUsing the SAMMS-MV Device Func- tions Using the Enter KeyUP and Down Keys ON/OFF Means warning Select ground fault pick-up currentDefault Value Select jam pickup current 120-400% Iflc F24 Loss of Load13 Entering and changing passwords SAMMS-MV Functions Program Mode/PasswordsF0 Ambient Temperature F1 Control Circuit Number and Incomplete Se- quence StatusF4 Full-Load Current for Overload Relay #1 Overload Setting Step Default Relay Size RangeF3 Size for Overload Relay #2 SAMMS-MVX Only 18 to 72AF7 Overload Trip Class F6 Service FactorF6A Motor Type F7A Cold Stall TimeF10 Display Time to Restart F8 Autoreset SAMMS-MVX OnlyF9 Phase Unbalance Protection F11 Emergency RestartingSize Pickup Current Default H3A-H3C 7A-I FLC 10A 20A F12 Ground Fault Protection or WarningF12A Ground Fault Pickup Current F13 Set Programmable Timer #1F17 Current Unbalance F21 Reset Motor DataF16 Trip Current F18 Display Total Elapsed Run Time of the MotorF23 Jam Protection SAMMS-MVX Only F25 Percentage of Motor Winding TemperatureF22 Process Current Warning Level SAMMS-MVX Only F23A Jam Pickup Current SAMMS-MVX OnlyF26 Baud Rate F27 AddressTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc