Appendix A Technical Specifications
Overload Specifications |
|
|
|
|
| ||
Overload classes | Overload classes 2 through 23 with one second increments. | ||
Trip Characteristics | Tripping time at 6 x IFLC = 95% of the overload class (±5%). | ||
| Tripping time at 1.5 x IFLC within two minutes for warm conditions for all classes. | ||
Tripping threshold | (1.1 ± 0.05) x IFLC for motors with 1.00 service factor, and | ||
| (1.2 ± 0.05) x IFLC for motors with 1.15 service factor. | ||
Tripping time | 20 minutes @1.15 x IFLC for motors with service factor 1. | ||
Mechanical jam protection | Sudden increase of the motor running current. | ||
400% in increments of 5% of IFLC . | |||
| Default values: 200% IFLC . |
| |
Loss of load protection | Sudden decrease of motor running current. | ||
increments of 5% of I FLC. | |||
| Default values: 50% I FLC. |
| |
Process current warning | Settings from 0 to 100% of IFLC. |
| |
|
|
| |
Accuracy | ± 5% of overload trip curve values. |
| |
| ± 2% repeat accuracy. |
| |
Phase unbalance protection | Response time after 1 second |
| |
| Shifted trip threshold value to 0.9 x IFLC at 40% phase unbalance. | ||
Equipment ground fault protection | Response time after 1.4 seconds. |
| |
|
| ||
|
|
| |
| Overload Relay Size | Default | |
| H3A | 7A- IFLC | 10A |
| H3B | 7A- IFLC | 10A |
| H3C | 7A- IFLC | 10A |
| H6 | 7A- I FLC | 20A |
Rotor protection | Cold stall time adjustable from 5 to 100 seconds in increments of 1 second. If cold stall | ||
| time is not known, default value shall be according to the type of motor used. | ||
| Motor Type |
| Cold Stall Time |
| Open Drip Proof (ODP) |
| 10 Seconds |
| Totally Enclosed Fan Cooled (EFC) | 20 Seconds | |
Ambient temperature | Motor ambient temperature adjustable 0 - 70°C in increments of 5°C. | ||
| Default value: 40°C. |
|
|
|
|
|
|
44