49

36.9"

A

.625" DIA x 2 TYP.

29.44"

TYP.

38"

FRONT SIDE

TOP VIEW

FRONT VIEW

25.59"

TYP.

NUT

JAM NUT

FOOT DETAIL A

NUT

SEE

HEIGHT

TABLE FOOT DETAIL B

B

2.47"

TYP

2.47"

TYP

B

MOUNTING PLATE

ALIGN FOOT PARALLEL TO

MOUNTING PLATE AS SHOWN

INSTALLATION NOTES:

 

 

 

 

 

 

Figure

 

 

 

 

 

 

 

1. CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.

 

 

 

 

 

 

37

2. INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE

 

 

 

 

Installation

FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS216001). USE M12-1.75X40mm CAP SCREW,

 

SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS.

 

 

 

 

 

 

 

3. LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS216001). INSTALL REAR

 

 

 

UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT

 

 

 

(FIG 1 AND FIG 2, PS216001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE

 

OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS216001). USE M12-1.75X40mm CAP

drawing,

SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. RETIGHTEN LEVELER FEET NUTS.

 

4. FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED.

 

 

 

INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS216000).

 

 

 

TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS AND

 

 

 

JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS216000). FLOOR STAND MUST BE LEVEL AND ALL FEET

 

 

seismic

MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD TRUBOLTS

 

 

 

 

 

EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.

 

 

 

 

 

 

 

5. ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET)

 

 

 

FIT INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH

 

 

floor

FLOOR STAND BRACKET (FIG. 2, DWG PS216002).

 

 

 

 

 

 

 

 

 

 

 

 

 

6. INSTALL THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS216002). ATTACH BRACKET TO STS2 USING

stand400-600A

M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 31 FT-LBS.

 

 

 

 

 

ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND

 

 

 

FLAT WASHER AND TORQUE TO 53 FT-LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HARDWARE TORQUE CHART

 

 

 

 

 

 

 

 

 

 

 

1.0" NUT

 

320 FT - LBS

 

 

 

 

 

M8 - 1.25

 

16FT - LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

M10 - 1.5

 

31 FT - LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

M12 - 1.75

 

53 FT -LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEIGHT TABLE

 

 

 

 

P/N OF FLOOR STAND:

HEIGHT

HEIGHT MAX:

 

HEIGHT MIN:

 

 

 

 

 

 

 

 

 

 

 

 

523405G1

18.0"

 

19.25"

 

16.75"

 

 

523406G1

24.0"

 

25.25"

 

22.75"

 

 

523407G1

30.0"

 

31.25"

 

28.75"

 

 

523408G1

36.0"

 

37.25"

 

374.75"

 

Installation

6" TYP.

BOTTOM VIEW

ISOMETRIC VIEW #1

PS216000 Rev.0

Drawings

Page 57
Image 57