Operating Instructions for the Touch Screen Interface
To manually select the preferred source:
1.Verify that the input breakers CB1 and CB2 are closed.
2.Select SOURCE XFERS from the menu bar.
The Select Preferred Source screen is displayed in the Event Display.
3.Check the Mimic to verify that Source 1 and Source 2 input voltages are correct.
4.Select SOURCE 1 or SOURCE 2 as your preferred source.
When conditions are correct, the switch transfers the load to the alternate source by selecting the alternate source as the preferred source.
This source is now monitored as the preferred source throughout the various configurations set up through the touch screen.
5.Verify that the correct source is designated as the preferred source and that the input source changes to the desired source.
The Mimic is updated to indicate the new preferred source. The source is now highlighted with blue and that source is labeled as the preferred source.
If the Transfer Inhibit message is displayed, check for alarm messages on the Active Status window. Correct alarm conditions before attempting a source transfer.
NOTE
The preferred source may also be changed via the optional Remote Source Selection option, thereby initiating a transfer remotely.
10.3Enabling Remote Source Selection
If your system is equipped with the optional Remote Source Selection option, it must be enabled. If you your system includes the Color Graphical Display:
1.Select CONFIG from the menu bar.
2.Select SYSTEM SETTINGS from the Configuration menu.
3.Select SYSTEM OPTIONS from the System Settings menu.
4.Select YES for the REMOTE SOURCE SELECT choice.
If your system contains the LED display or you are configuring the system from the
12.1 - Using the
10.4Maintenance Bypass
The STS2 is equipped with two
However, the unit can be bypassed using a
In the event of source or switch failure, the unit should be bypassed only to the current input source. For convenience, instructions for the bypass procedure can be displayed on the touch screen by select- ing the BYP. PROC option from the menu bar.
The Mimic is used to verify the status of the unit during the bypass procedures. In the unlikely event that the Color Graphical Display is not available, open the front door and look through the slots in the control door. If you can see green LEDs on the gate driver board through that slot, then the unit is connected to the source referenced on the label below that slot. See Figure 48.
67