18
(965)
38.0
CENTER |
|
|
| |||
(1956) | ||||||
GRAVITY | ||||||
|
|
| 77.0 | |||
|
|
| ||||
|
|
|
|
|
|
(923)
36.3
AIR INTAKE AREA
DO NOT BLOCK
(474) |
| AIR FILTER |
18.6 |
| |
|
|
FRONT VIEW
(815)NOTES:
32.1
1.ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
2.18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
3.INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
4.HEAT OUTPUT: 6970 BTU/HR (2.04 KW/HR) MAX. FOR 400A SWITCH. 10520 BTU/HR (3.08 KW/HR) MAX. FOR 600A SWITCH.
5.WEIGHT - 1200 LBS. (544 KG))
6.UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
7.KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
8.COLOR - IBM OFF WHITE.
9.OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
10.THREADED MOUNTING HOLES (SEE DETAIL A) ARE PROVIDED FOR SEISMIC
CENTER | ANCHORING OR FLOOR STAND. MOUNTING BOLTS MUST BE THREADED INTO |
GRAVITY | THE UNIT MOUNTING HOLES FROM UNDERNEATH THE UNIT BASE. IF FLOOR |
| |
| STAND IS USED, THE CASTERS MUST REST ON THE FLOOR STAND TO |
| SUPPORT THE WEIGHT OF THE UNIT. |
|
| (69.8) |
| 12MM DIA THREADED | 2.75 (TYP) |
| MOUNTING HOLE (4) TYP |
|
(372) | (SEE NOTES 10) |
|
14.6 |
|
|
SIDE VIEW |
|
|
|
| LEVELER |
Figure 6 Outline drawing: 400 – 600 amp STS2
(794) CASTER
CONTROL CABLE31.3 CENTERS BOTTOM ENTRY AREA
SEE DETAIL A
DETAIL A |
(116)
4.6
FRONT
(292)
11.5
12MM
|
|
|
|
|
| FRONT OF UNIT SHOWN |
|
|
|
|
|
| |
| (910) |
|
|
| WITHOUT SIDE PANEL | |
POWER | 35.8 | CABLE |
|
|
|
|
(399) | ||||||
TOP ENTRY AREA | 15.7 |
(343) |
|
|
|
|
|
| (267) | ||
13.5 |
|
|
|
|
|
|
|
| 10.5 |
| |||||||||
|
| POWER CABLE |
(544)BOTTOM ENTRY (337)
21.4 |
| AREA | 13.3 | ||||
(435) | |||||||
|
|
|
|
| |||
|
| 17.1 |
|
|
|
|
(88) 3.5
(825)
32.5
BOTTOM VIEW
CENTERS (736)
CASTER 29.0 CENTERS
(548)
21.6
(25)AIR
.97 REF | EXHAUST |
12MM CENTERS |
|
(130) |
5.1 |
(326)
12.8
FRONT
CONTROL CABLE
TOP ENTRY AREA
(752)(198)
29.6 | 7.8 MAX. DOOR SWING 180° (TYP) |
TOP VIEW
Installation
OUTLINE DRAWING
400 - 600 AMP
STATIC TRANSFER SWITCH 2
PS211400 REV. NO. 1