Installation Drawings
20
Figure 8 Outline drawing: 100 – 250amp STS2 with a key lockout switch option
GRAVITY
SIDE VIEW
TOP VIEW
BOTTOM ENTRY AREA
POWER CABLE
BOTTOM ENTRY AREA
CONTROL CABLE
BOTTOM VIEW
FRONT VIEW
EXHAUST
TOP ENTRY AREA
TOP ENTRY AREA
POWER CABLE
CONTROL CABLE
FRONT
FRONT
MAX. DOOR SWING 180°
CENTER
GRAVITY
CENTER
SEE DETAIL A
CENTERS
CASTER
CENTERS
12MM
AIR
CENTERS
CASTER
12MM CENTERS
AIR FILTER
AIR INTAKE AREA
DO NOT BLOCK
OUTLINE DRAWING
100 - 250 AMP WITH KEY LOCKOUT SWITCH OPTION
STATIC TRANSFER SWITCH 2
KEY
LOCKOUT
SWITCH
NOTES:
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
2. 18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
3. INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
4. HEAT OUTPUT: 2710 BTU/HR (0.80 KW/HR) MAX. FOR 100A SWITCH.
4680 BTU/HR (1.37 KW/HR) MAX. FOR 250A SWITCH.
5. WEIGHT - 780 LBS. (354 KG)
6. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
7. KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
8. COLOR - IBM OFF WHITE.
9. OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
10. THREADED MOUNTING HOLES (SEE DETAIL A) ARE PROVIDED FOR SEISMIC
ANCHORING OR FLOOR STAND. MOUNTING BOLTS MUST BE THREADED INTO
THE UNIT MOUNTING HOLES FROM UNDERNEATH THE UNIT BASE. IF FLOOR
STAND IS USED, THE CASTERS MUST REST ON THE FLOOR STAND TO
SUPPORT THE WEIGHT OF THE UNIT.
FRONT OF UNIT SHOWN
WITHOUT SIDE PANEL
DETAIL A
MOUNTING HOLE (4) TYP
(SEE NOTES 10)
12MM DIA THREADED
LEVELER
(620)
24.4
(238)
9.4
(343)
13.5
(326)
12.8
(130)
5.1
(756)
29.8
(736)
29.0
(548)
21.6
(272)
10.7
(488)
19.2
(815)
32.1
(1956)
77.0
(477)
18.8
(594)
23.4
(280)
11.1
(213)
8.4
(116)
4.6
(932)
36.7
(762)
30
(619)
24.4
(265)
10.4
(376)
14.8
(546)
21.5
PS211101 REV. NO. 1