"NO CUSTOMER CONNECTION"

1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16

J51

INPUT CONTACT ISOLATOR BOARD

02-810012-XX

TABLE (J51)

 

INPUT

 

PIN NO.

 

CONTACT

 

 

1

 

1

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

2

 

3

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

3

 

5

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

4

 

7

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

5

 

9

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

6

 

11

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

7

 

13

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

8

 

15

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

NOTES:

1.CUSTOMER CONTROL WIRING CONNECTION POINTS ARE TERMINALS 1 THROUGH 16 (SEE TABLE J51).

2.CUSTOMER PROVIDED NORMALLY OPEN DRY CONTACTS FOR USER ALARM MESSAGES.

3.REFER TO INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR CONFIGURING THE INPUT CONTACT ISOLATOR BOARD OPTION.

4.ALL CONTROL WIRING (BY OTHERS) MUST BE RUN SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

5.REFER TO STATIC TRANSFER SWITCH CONTROL CONNECTION DIAGRAM FOR LOCATION OF INPUT CONTACT ISOLATOR BD. OPT.

6.SIGNAL VOLTAGE: 100mAMP @ 12VDC.

7.MAXIMUM CABLE LENGTH 500 FT. (152 METERS) WITH

#16AWG FLEXIBLE STRANDED CABLE.

8.ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

PS213002

Rev. 2

Figure 25 Control wiring for the input contact isolator board option