Alarm and Faults
The History Log has the following fields:
•Replay Rate — indicates how long it takes for the replay to play. Use the UP and DOWN buttons to set the time.
•Status — the status of the STS2 at the point of the current frame in the replay. The History log has three statuses: Frozen, Not Frozen and Retrieving Data, please stand by.
•Critical Event — The event which triggered this log to be written. The event is indicated in red on the bar graph.
•Frame Number — the current frame in the replay. A negative number indicates the replay is at a point before the triggering event occurred.
11.3Alarm Notes
The
In the auto reset mode, the alarm is reset as soon as the load current and source voltage return to nor- mal, and transfers are no longer inhibited. In manual mode, the alarm remains active and transfers are inhibited until the conditions return to normal and the user manually presses the RESET button (ALRMRST button on LED units). In either case, the cause of the Source 1 or Source 2
These events indicate a device failure. The device must be replaced and the system must be restarted for the fault to clear. A shorted SCR automatically trips open a source input switch (CB1 or CB2) to prevent transfers in the event of an SCR failure. The SCR failure must be investigated and repaired before returning the switch to normal operation. Both source input switches must be opened (such as when the unit is placed in maintenance bypass for servicing) before a shorted or open SCR alarm can be reset.