36.9"

83.9"

TOP VIEW

NUT

JAM NUT

FOOT DETAIL A

NUT

INSTALLATION NOTES:

1.CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.

2.INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS217001).

USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS.

3.LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS217001). INSTALL REAR UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT (FIG 1 AND FIG 2, PS217001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS217001). USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO

53 FT-LBS. RETIGHTEN LEVELER FEET NUTS.

4.FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS217000). TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS AND JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS217000). FLOOR STAND MUST BE LEVEL AND ALL FEET MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD TRUBOLTS EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.

5.ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) FIT INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR STAND BRACKET (FIG. 2, DWG PS217002).

Figure 41 Installation drawing, seismic floor

53

SEE HEIGHT

TABLE

A

2.47"

TYP.

29.44"

TYP.

6" TYP.

FRONT VIEW

71.55"

TYP.

MOUNTING

PLATE

ALIGN FOOT PARALLEL

TO MOUNTING PLATE AS

SHOWN

BOTTOM VIEW

 

FOOT DETAIL B

6. INSTALL THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS217002). ATTACH BRACKET TO STS2

stand

 

 

 

 

USING M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO

 

 

 

 

 

31 FT-LBS. ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER,

 

 

 

 

 

AND FLAT WASHER AND TORQUE TO 53 FT-LBS

 

800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

-1000A

 

 

 

 

 

 

 

 

 

 

RIGHT SIDE VIEW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.47"

 

HARDWARE TORQUE CHART

 

 

 

 

 

 

 

 

 

 

 

 

 

TYP

 

1.0" NUT

 

 

320 FT - LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M8 - 1.25

 

 

16FT - LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M10 - 1.5

 

 

31 FT - LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M12 - 1.75

 

 

53 FT -LBS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEIGHT TABLE

 

 

 

 

 

P/N OF FLOOR STAND:

HEIGHT

HEIGHT MAX:

HEIGHT MIN:

 

 

 

523409G1

18.0"

19.25"

16.75"

ISOMETRIC VIEW

 

 

523410G1

24.0"

25.25"

22.75"

 

 

 

523411G1

30.0"

31.25"

28.75"

 

 

 

523412G1

36.0"

37.25"

34.75"

 

 

PS217000 Rev. 0

Installation Drawings

Page 61
Image 61
Liebert POWER PROTECTION STATIC TRANSFER SWITCH manual Installation drawing, seismic floor, 800