POWER TERMINAL BLOCK
NOTES:
Figure
RECOMMENDED LOCATION FOR CUSTOMER CONNECTION
OF INPUT POWER
A
B
LOCATION OF FACTORY SUPPLIED INPUT POWER CABLE ASSEMBLY.
1. TWO JUNCTION BOXES ARE SUPPLIED, ONE FOR |
EACH INPUT. |
2. CABLE(S) ARE FACTORY SUPPLIED TO CONNECT |
THE JUNCTION BOX TO THE INPUT BUSBARS. SEE |
ELECTRICAL FIELD CONNECTIONS DRAWING FOR |
LOCATION. |
30 Outline drawing
42
RACEWAY (BY OTHERS)
3 PHASE, 3 WIRE PLUS GROUND.
C
G
INPUT JUNCTION BOX
B |
| G DIA. |
| HOLE | |
|
|
H
A
D
C
3. PARALLEL CABLES ARE USED ON 400A AND 600A |
UNITS. |
for input junction box
|
|
|
| INPUT JUNCTION BOX |
|
|
|
|
| |
RATING |
|
|
| DIMENSIONAL DATA - INCHES [mm] |
|
|
| WIRE SIZE RANGE |
| |
A | B | C | D | E | F | G | H |
| ||
|
| PS211005 | ||||||||
100A | 16 [406] | 14 [356] | 6 [152] | 17 1/2 [445] | 12 [305] | 16 3/4 [426] | 5/16 [8] | 1 [25] | #6 AWG TO #2/0 AWG | |
250A - 600A | 16 [406] | 30 [762] | 6 [152] | 33 [830] | 10 [254] | 32 [813] | 7/16 [11] | 3 [76] | (2) #6 AWG TO (2) 500 kcmil | Rev. 1 |
Installation Drawings