45

29.9"

36.9"

TOP VIEW

SEE HEIGHT

TABLE

AFRONT VIEW

.625" DIA x 2

 

17.48"

 

 

 

 

TYP.

TYP.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.47"

TYP.

29.44"

TYP.

NUT

JAM NUT

FOOT DETAIL A

NUT

FOOT DETAIL B

2.47"

TYP

MOUNTING PLATE

ALIGN FOOT PARALLEL TO

MOUNTING PLATE AS SHOWN

INSTALLATION NOTES:

1.CHECK ALL HARDWARE FOR PROPER TORQUE PRIOR TO INSTALLATION.

2.INSTALL REAR LOWER STS2 BRACKET TO THE FLOOR STAND USING EXISTING HOLES WITH BENT FLANGE FACING THE FRONT OF THE FLOOR STAND (FIG. 3 AND FIG 4, DWG PS215001). USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS.

3.LOOSEN THE STS2 ADJUSTABLE LEVELER FEET NUTS (SEE DETAIL C; DWG PS215001). INSTALL REAR UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH TABS FACING OUT

(FIG 1 AND FIG 2, PS215001). INSTALL FRONT UPPER STS2 BRACKET USING EXISTING HOLES ON UNDERSIDE OF THE STS2 WITH BENT FLANGE FACING TO THE FRONT. (FIG.1 AND FIG 2, PS215001). USE M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 53 FT-LBS. RETIGHTEN LEVELER FEET NUTS.

4.FLOOR STAND CAN BE MOUNTED NEXT TO A WALL IF NEEDED, REAR ACCESS NOT REQUIRED. INSTALL FLOOR STAND WITH FEET ORIENTATED AS SHOWN IN (BOTTOM VIEW; DWG PS215000).

TO ADJUST VERTICAL HEIGHT OF FLOOR STAND FEET, LOOSEN, ADJUST AND TIGHTEN THE NUTS AND JAM NUT SHOWN IN (FOOT DETAIL A & B; ON DWG PS215000). FLOOR STAND MUST BE LEVEL AND ALL FEET MUST BE TOUCHING THE FLOOR. ATTACH FLOOR STAND FEET USING 1/2" X 4" RED HEAD TRUBOLTS EXPANSION ANCHORS (FEILD SUPPLIED) (2) PER FOOT.

5.ROLL THE STS2 ONTO THE FLOOR STAND SO THAT THE TABS ON THE (REAR UPPER STS2 BRACKET) FIT INTO THE SLOTS ON THE (REAR LOWER STS2 BRACKET). TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR STAND BRACKET (FIG. 2, DWG PS215002).

6.INSTALL THE LOWER FRONT BRACKETS (FIG 1, DETAIL A; DWG PS215002). ATTACH BRACKET TO STS2 USING M10-1.50X30mm CAP SCREW, SPLIT LOCK WASHER, AND FLAT WASHER AND TORQUE TO 31 FT-LBS. ATTACH BRACKET TO FLOOR STAND USING M12-1.75X40mm CAP SCREW, SPLIT LOCK WASHER, AND

FLAT WASHER AND TORQUE TO 53 FT-LBS

B

HARDWARE TORQUE CHART

 

 

 

 

1.0" NUT

320 FT - LBS

 

M8 - 1.25

16FT - LBS

 

 

 

 

M10 - 1.5

31 FT - LBS

 

 

 

 

M12 - 1.75

53 FT -LBS

 

 

 

HEIGHT TABLE

P/N OF FLOOR STAND:

HEIGHT

HEIGHT MAX:

HEIGHT MIN:

523401G1

18.0"

19.25"

16.75"

523402G1

24.0"

25.25"

22.75"

523403G1

30.0"

31.25"

28.75"

523404G1

36.0"

37.25"

34.75"

Figure 33 Installation drawing, seismic floor stand 100-250A

6" TYP.

BOTTOM VIEW

ISOMETRIC VIEW 250A FLOOR STAND

INSTALLATION DRAWING FOR SEISMIC FLOOR STAND 100-250A STS2

PS215000 REV. NO. 0

Installation Drawings

Page 53
Image 53
Liebert POWER PROTECTION STATIC TRANSFER SWITCH manual Installation drawing, seismic floor stand 100-250A