Liebert POWER PROTECTION STATIC TRANSFER SWITCH For internal modem wiring, Sitescan, See Detail B

Models: POWER PROTECTION STATIC TRANSFER SWITCH

1 152
Download 152 pages 17.94 Kb
Page 46
Image 46

38

CUSTOMER SUPPLIED

INTERCONNECTING CABLE

TO EXTERNAL MODEM

SEE NOTE 2

1 2 3 4 5 6 7 8 9

J81

DETAIL A

EXTERNAL MODEM

SEE DETAIL A

J81

J1A

NOTES:

1.MAXIMUM CABLE LENGTH 1000 FEET (300 METERS) WITH TWISTED PAIR CABLE #22 AWG 300V MINIMUM.

2.SIGNAL VOLTAGE 5VDC, CURRENT 10mA.

3.REFER TO INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR CONFIGURING THE COMMS BOARD.

4.ALL CONTROL WIRING (BY OTHERS) MUST BE RUN SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT.

5.REFER TO CONTROL CONNECTION LOCATION DIAGRAM OF STATIC TRANSFER SWITCH FOR LOCATION OF COMMS BOARD.

6.ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

CUSTOMER SUPPLIED

INTERCONNECTING

CABLE TO SITESCAN

SEE NOTES 1 & 2

Figure 26 Control wiring for comms board (see Figure 27 on page

TB51

TB55

TB56

NO CUSTOMER

SITESCAN

NO CUSTOMER

CONNECTION

SEE DETAIL B

CONNECTION

COMMS BOARD 02-810015-XX

+

-

12 3

TB55

DETAIL B

PS213003 Rev. 2

39 for internal modem wiring)

Installation Drawings

Page 46
Image 46