40
| ||
| CONNECTOR) FOR | |
"NO CUSTOMER | SETUP ONLY. USES | |
STANDARD COMPUTER | ||
CONNECTION" | ||
SERIAL PORT CABLE | ||
|
J3
P18
1 | 2 3 | TB2 |
|
"NO CUSTOMER | NETWORK INTERFACE |
CONNECTION" | |
+ - | CARD (NIC) 416241GX |
SEE NOTE 2 |
|
CUSTOMER SUPPLIED |
|
INTERCONNECTING |
|
CABLE TO MODBUS |
|
NOTES:
1.WIRE SIZE AND TYPE: 10/100
2.MAXIMUM CABLE LENGTH 1000 FEET (300 METERS) WITH TWISTED PAIR CABLE #22 AWG MINIMUM. SIGNAL VOLTAGE 5VDC, CURRENT 10mA.
3.REFER TO INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR CONFIGURING THE NETWORK INTERFACE CARD (NIC).
4.ALL CONTROL WIRING (BY OTHERS) MUST BE RUN SEPARATE FROM POWER WIRING. CONTROL WIRING RUNS SHOULD NOT BE COMBINED IN THE SAME CONDUIT.
5.REFER TO CONTROL CONNECTION LOCATION DIAGRAM OF STATIC TRANSFER SWITCH FOR LOCATION OF NETWORK INTERFACE CARD OPTION.
6.ALL WIRING MUST BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.
ETHERNET NETWORK | CUSTOMER SUPPLIED |
INTERCONNECTING CABLE | |
SEE NOTES 1 & 2 |
|
PS213005
REV. 2
Figure 28 Control wiring for the network interface card (NIC) option
Installation Drawings