(762)

(815)

 

 

30

32.1

 

 

 

 

NOTES:

1.ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.

2.18” (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.

3.INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.

4.HEAT OUTPUT: 2710 BTU/HR (0.80 KW/HR) MAX. FOR 100A SWITCH.

4680 BTU/HR (1.37 KW/HR) MAX. FOR 250A SWITCH.

Figure 5 Outline

7.0 INSTALLATION

CENTER

GRAVITY

(932)

36.7

(1956)

CENTER

GRAVITY

77.0

 

5.WEIGHT - 780 LBS. (354 KG).

6.UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.

7.KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.

8.COLOR - IBM OFF WHITE.

9.OPEN DOOR TO REPLACE AIT FILTER, DISPOSABLE TYPE, SIZE 1X25X25.

10.THREADED MOUNTING HOLES (SEE DETAIL A) ARE PROVIDED FOR SEISMIC ANCHORING OR FLOOR STAND. MOUNTING BOLTS MUST BE THREADED INTO THE UNIT MOUNTING HOLES FROM UNDERNEATH THE UNIT BASE. IF FLOOR STAND IS USED, THE CASTERS MUST REST ON THE FLOOR STAND TO SUPPORT THE WEIGHT OF THE UNIT.

(69.8)

drawing: 100 – 250 amp STS2

DRAWINGS

17

(477)

18.8

FRONT VIEW

AIR INTAKE AREA

 

DO NOT BLOCK

(488)

AIR FILTER

 

19.2

SIDE VIEW

12MM DIA THREADED MOUNTING HOLE (4) TYP

(SEE NOTES 10)

2.75 (TYP)

 

(594) CASTER

 

 

 

 

 

23.4 CENTERS

 

 

 

(620)

(213)

(280)

 

SEE DETAIL A

 

24.4

8.4

11.1

 

 

 

(116)

 

 

 

 

 

4.6

FRONT

 

 

 

(238)

 

 

 

 

 

CONTROL CABLE

(272)

 

 

12MM

9.4

BOTTOM ENTRY AREA

CENTERS

 

10.7

 

 

(736)

 

 

CASTER

 

 

POWER CABLE

 

 

29.0

 

 

CENTERS

 

 

BOTTOM ENTRY AREA

(376)

(548)

 

 

 

21.6

 

 

 

(546)

14.8

 

AIR

 

 

 

 

21.5

(265)

 

 

EXHAUST

FRONT

 

10.4

 

 

 

 

 

 

 

LEVELER

POWER CABLE

DETAIL A

TOP ENTRY AREA

 

FRONT OF UNIT SHOWN

 

WITHOUT SIDE PANEL

(343)

13.5

(326)

12.8

(619)

12MM CENTERS

 

(130)

CONTROL CABLE

(756)

TOP ENTRY AREA

5.1

24.4

 

 

 

MAX. DOOR SWING 180° 29.8

 

 

 

 

 

 

BOTTOM VIEW

 

TOP VIEW

 

 

OUTLINE DRAWING

100 - 250 AMPPS211100 REV. NO. 2

STATIC TRANSFER SWITCH 2

Installation Drawings

Page 25