(762) | (815) | ||
|
| 30 | 32.1 |
|
|
|
|
NOTES:
1.ALL DIMENSIONS ARE IN INCHES AND MILLIMETERS.
2.18” (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
3.INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
4.HEAT OUTPUT: 2710 BTU/HR (0.80 KW/HR) MAX. FOR 100A SWITCH.
4680 BTU/HR (1.37 KW/HR) MAX. FOR 250A SWITCH.
Figure 5 Outline
7.0 INSTALLATION
CENTER
GRAVITY
(932)
36.7
(1956) | CENTER |
GRAVITY | |
77.0 |
|
5.WEIGHT - 780 LBS. (354 KG).
6.UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
7.KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
8.COLOR - IBM OFF WHITE.
9.OPEN DOOR TO REPLACE AIT FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
10.THREADED MOUNTING HOLES (SEE DETAIL A) ARE PROVIDED FOR SEISMIC ANCHORING OR FLOOR STAND. MOUNTING BOLTS MUST BE THREADED INTO THE UNIT MOUNTING HOLES FROM UNDERNEATH THE UNIT BASE. IF FLOOR STAND IS USED, THE CASTERS MUST REST ON THE FLOOR STAND TO SUPPORT THE WEIGHT OF THE UNIT.
(69.8)
drawing: 100 – 250 amp STS2
DRAWINGS
17
(477)
18.8
FRONT VIEW
AIR INTAKE AREA |
|
DO NOT BLOCK | (488) |
AIR FILTER | |
| 19.2 |
SIDE VIEW
12MM DIA THREADED MOUNTING HOLE (4) TYP
(SEE NOTES 10)
2.75 (TYP)
| (594) CASTER |
|
|
|
|
| 23.4 CENTERS |
|
|
| (620) |
(213) | (280) |
| SEE DETAIL A | ||
| 24.4 | ||||
8.4 | 11.1 |
|
|
| |
(116) |
|
|
|
|
|
4.6 | FRONT |
|
|
| (238) |
|
|
|
|
| |
CONTROL CABLE | (272) |
|
| 12MM | 9.4 |
BOTTOM ENTRY AREA | CENTERS |
| |||
10.7 |
|
| (736) |
| |
| CASTER |
|
| ||
POWER CABLE |
|
| 29.0 |
| |
| CENTERS |
|
| ||
BOTTOM ENTRY AREA | (376) | (548) |
|
|
|
21.6 |
|
|
| ||
(546) | 14.8 |
| AIR |
| |
|
|
| |||
21.5 | (265) |
|
| EXHAUST | FRONT |
| 10.4 |
|
| ||
|
|
|
|
|
LEVELER
POWER CABLE | DETAIL A |
TOP ENTRY AREA | |
| FRONT OF UNIT SHOWN |
| WITHOUT SIDE PANEL |
(343)
13.5
(326)
12.8
(619) | 12MM CENTERS |
| (130) | CONTROL CABLE | |
(756) | TOP ENTRY AREA | ||||
5.1 | |||||
24.4 |
|
| |||
| MAX. DOOR SWING 180° 29.8 |
|
| ||
|
|
|
| ||
BOTTOM VIEW |
| TOP VIEW |
|
|
OUTLINE DRAWING
100 - 250 AMPPS211100 REV. NO. 2
STATIC TRANSFER SWITCH 2
Installation Drawings