.51 DIA.

 

 

 

PEM NUT

 

 

GROUND BUS

INPUT/OUTPUT BUS

FRONT VIEW

RIGHT SIDE VIEW

 

NOTES:

 

1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).

 

2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH

 

REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

 

CONDUIT SIZE, AND REPLACE.

 

3. CONTROL WIRING AND POWER WIRING MUST BE RUN

 

IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

 

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.

 

4. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE

 

NOT RECOMMENDED.

 

5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL

PEM NUT

AND LOCAL ELECTRICAL CODES.

6.HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT, NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR

Figure 16 Electrical field connections

28

CB1

CB4

NEUTRAL

BUS

GROUND

BUS

FRONT VIEW

(WITH FRONT PANELS REMOVED)

SOURCE 1 INPUT Ø A, Ø B, Ø C

SOURCE 2 INPUT

ØA, Ø B, Ø C

CB2

CB5

SYSTEM OUTPUT Ø A, Ø B, Ø C

CB3

FRONT

NEUTRAL BUS

CONNECTING CABLES TO THE BUS BARS.

 

RIGHT SIDE VIEW

7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS

 

428 INCH-LBS. (48 N-m).

 

 

SOURCE 1 INPUT Ø A

 

 

 

SOURCE 1 INPUT Ø B

 

 

 

SOURCE 1 INPUT Ø C

 

 

 

NEUTRAL BUS

 

 

 

 

SOURCE 1

 

SOURCE 2

 

CB1

 

CB2

 

 

K1

 

K2

 

K2 K3

CB4

CB3

K1 K3

CB5

SYSTEM OUTPUT

ONE-LINE DIAGRAM

SECTION A-A

SIDE VIEW

PS212400

Rev. 2

drawing: 400 – 600 amp STS2 with single output breaker

Installation Drawings

Page 36
Image 36
Liebert POWER PROTECTION STATIC TRANSFER SWITCH manual Drawing 400 600 amp STS2 with single output breaker