32

STATIC TRANSFER SWITCH 2, MOLDED CASE BREAKER SCHEDULE

STS2

VENDOR

TYPE

AMPACITY

 

WITHSTAND

RATING

VOLTAGE

CURRENT

 

 

 

 

 

 

 

 

 

 

MERLIN GERIN

NSF

 

200-240V

100K

100A

150A

380-480V

65K

 

 

 

 

600V

25K

 

 

 

 

 

 

 

MERLIN GERIN

NSF

 

200-240V

100K

250A

250A

380-480V

65K

 

 

 

 

600V

25K

 

 

 

 

 

 

400A

MERLIN GERIN

NSJ

 

200-240V

100K

400A

380-480V

100K

 

 

 

 

600V

25K

 

 

 

 

 

 

600A

MERLIN GERIN

NSJ

 

200-240V

100K

600A

380-480V

100K

 

 

 

 

600V

25K

 

 

 

 

 

 

 

SQD

PJ

 

200-240V

100K

800A

800A

380-480V

65K

 

 

 

 

600V

25K

 

 

 

 

 

 

 

SQD

PJ

 

200-240V

100K

1000A

1200A

380-480V

65K

 

 

 

 

600V

25K

 

 

 

 

 

 

NOTES:

1.THE STS2 AUTOMATIC MOLDED CASE BREAKERS ARE 3 POLE, 600VAC RATED WITH MAGNETIC TRIP ONLY.

2.UPSTREAM DEVICES (BY OTHERS) MUST BE USED TO PROVIDE OVERCURRENT PROTECTION. UPSTREAM OVERCURRENT PROTECTION SHOULD HAVE AMPACITY EQUAL TO OR LESS THAN THE AMPERE RATING OF THE STATIC SWITCH MOLDED CASE BREAKER.

CIRCUIT BREAKER SCHEDULE

PS214000 REV. NO. 3

100AMP TO 1000AMP

 

STATIC TRANSFER SWITCH 2

 

Figure 20 Circuit breaker schedule

Installation Drawings

Page 40
Image 40
Liebert POWER PROTECTION STATIC TRANSFER SWITCH manual Static Transfer Switch 2, Molded Case Breaker Schedule