Siemens F22 Process Current Warning Level SAMMS-MVX Only, F23 Jam Protection SAMMS-MVX Only

Page 40

3 Operating the SAMMS-MV Device

F22 - Process Current Warning Level (SAMMS-MVX Only)

1.Press the LIST key to view the active process current level. The value represents the percentage of the full load current setting above which a motor current causes the External Trip LED to flash. The function is disabled for five times the class time after starting, or after a speed or direction change. The range of settings is in 1% increments from zero (OFF) through 100. The factory default is OFF.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key until the desired setting is displayed then press the ENTER key to select the setting. The display blanks while the ENTER key is pressed.

3. Return to Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to go to other functions.

F23 Jam Protection (SAMMS-MVX Only)

1.Press the LIST key to view the active jam protection setting (ON or OFF). The factory default setting is ON. If jam protection is enabled (ON) and the motor running current increases to the pickup current value within 360 msec, the motor will trip off-line and the External Trip LED is steadily lit. The function is disabled for five times the class time after starting, or after a speed or direction change.

2.To change the setting, you must be in program mode.

3.To change the protection setting, press the UP or DOWN key to display ON or OFF, then press ENTER to select the setting that is shown. The display blanks while the ENTER key is pressed.

4.Return to Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F23A Jam Pickup Current (SAMMS-MVX Only)

1.Press the LIST key to view the jam current pickup value in use. The range of possible values is between 120% and 400% to the FLC, in increments of 5%. The factory default is 200%.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key until the desired setting is displayed then press the ENTER key to select the setting. The display blanks while the ENTER key is pressed.

4.To exit the program mode, press and hold the (F)unction key

for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

5. Press the (F)unction key to step through to another function.

F24 - Loss of Load Protection or Warning (SAMMS-MVX Only)

1.Press the LIST key to view the active loss of load setting (ON or OFF). The factory default setting is warning (OFF), and the other setting is protection (ON). This function is disabled for five times the class time after starting or speed or direction changes.

a.When protection (ON) is selected and the motor current drops below the pickup current value, within 360 msec, the External Trip LED will light and the SAMMS-MV trips.

b.When warning (OFF) is selected and the motor current drops below the pickup current value within 360 msec, the External Trip LED flashes but the SAMMS-MV does not trip.

2.To change the setting, you must be in program mode.

3.To change the protection setting, press the UP or DOWN key to display ON or OFF options, then press ENTER to select the setting that is shown. The display blanks while the ENTER key is pressed.

4.Return to Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to step through to another function.

F24A - Loss of Load Pickup Current (SAMMS-MVX Only)

1.Press the LIST key to view the active setting. The range of possible values is between 20% and 95% to the FLC, in increments of 5%. The factory default is 50%.

2.To change the setting, you must be in program mode.

3.To change the setting, press the UP or DOWN key until the desired setting is displayed then press the ENTER key to select the setting. The display blanks while the ENTER key is pressed.

4.Return to Step 3 if you select an incorrect setting.

5.To exit the program mode, press and hold the (F)unction key for several seconds. The display will show “Prog.” Press the UP or DOWN key to change to the display mode.

6.Press the (F)unction key to go to other functions.

F25 - Percentage of Motor Winding Temperature

1.Press the LIST key to view the temperature of the motor windings as a percentage of the steady-state, full-load winding temperature. The maximum allowable winding tem- perature percentage is 175%.

38

Image 40
Contents SAMMS-MV Qualified Person Contents Field Service Operation Signal WordsQualified Person About this Manual SAMMS-MV Device Models Advanced Protection for Medium-Voltage MotorsOverload Protection Using the Standardized Control PanelProgramming Control Circuits Change settings requires password Yes Remote inputs One SAMMS-MV ModelOutputs One Light barsInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Password Protection Using the Reset/Test Push ButtonPerforming a Lamp Test Performing an Overload Relay TestOutput Devices Input DevicesLadder Diagrams Library of Standard Ladder Diagrams Custom Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Ridethrough Upon Loss of Power SAMMS-MVX Only Motor Ambient TemperatureIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-MVX OnlyODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Ultimate Trip Level and Service Factor Phase UnbalanceDual Overload Protection SAMMS-MVX Only Jam Protection SAMMS-MVX OnlyGround Fault Detection Repetitive StartsStart Inhibit Cooling Time Constants12 Multi-start scenario for an ODP motor Autoreset After a Trip SAMMS-MVX Only Using the Hand Held Communicator HHCEmergency Restarting Function Key5A CT primary current low speed if used Service factor Function Number5A CT primary current if used Full load current for OLR No Motor type Overload trip class class 2 throughUsing the SAMMS-MV Device Func- tions Using the Enter KeyUP and Down Keys ON/OFF Select ground fault pick-up current Default ValueMeans warning Select jam pickup current 120-400% Iflc F24 Loss of Load13 Entering and changing passwords Program Mode/Passwords F0 Ambient TemperatureSAMMS-MV Functions F1 Control Circuit Number and Incomplete Se- quence StatusOverload Setting Step Default Relay Size Range F3 Size for Overload Relay #2 SAMMS-MVX OnlyF4 Full-Load Current for Overload Relay #1 18 to 72AF6 Service Factor F6A Motor TypeF7 Overload Trip Class F7A Cold Stall TimeF8 Autoreset SAMMS-MVX Only F9 Phase Unbalance ProtectionF10 Display Time to Restart F11 Emergency RestartingF12 Ground Fault Protection or Warning F12A Ground Fault Pickup CurrentSize Pickup Current Default H3A-H3C 7A-I FLC 10A 20A F13 Set Programmable Timer #1F21 Reset Motor Data F16 Trip CurrentF17 Current Unbalance F18 Display Total Elapsed Run Time of the MotorF25 Percentage of Motor Winding Temperature F22 Process Current Warning Level SAMMS-MVX OnlyF23 Jam Protection SAMMS-MVX Only F23A Jam Pickup Current SAMMS-MVX OnlyF26 Baud Rate F27 AddressTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc