3 Operating the SAMMS-MV Device

Figure 3.6 Rotor and winding temperature during 10 second motor stall

temperature. You can select ambient temperature from 0° to 70°C in increments of 5°C, with HHC function F0.

Important: Do not use this feature with motors rated for ambient temperature other than the standard 40°C.

3.12Protection Curves and Overload Classes

The specific motor protection curve selected depends upon the overload class setting. The overload class is defined as the maximum tripping time in seconds for a current level of 600% of the full-load current or IFLC. (The typical starting current of motors is 600% of IFLC.) For example, an overload class setting of 10 guarantees that a current of 600% of IFLC will cause a trip in 10 seconds or less. In the SAMMS-MV, the protection curves

are designed to cause a trip in 90% to 100% of the class time for a current of 600% of IFLC.

The lowest overload class, greater than or equal to the motor’s starting time, gives the best protection. Overload classes 2 through 23 are available in SAMMS-MV. The range of protec- tion curves are shown in Figures 3.7 through 3.10.

Important: In the unlikely event that the motor acceleration time (overload class) exceeds the motor’s stall time, use a speed switch as an input source to open the contactor if the switch senses a locked rotor or stall condition.

Note: For clarity, the time-current characteristic curves in this manual are shown with overload classes 2, 5, 10, 15 and 23 only. Use interpolation to derive values of other overload classes not shown.

19

Image 21
Contents SAMMS-MV Qualified Person Contents Signal Words Field Service OperationQualified Person About this Manual Advanced Protection for Medium-Voltage Motors SAMMS-MV Device ModelsUsing the Standardized Control Panel Overload ProtectionProgramming Control Circuits SAMMS-MV Model Change settings requires password Yes Remote inputs OneOutputs One Light barsInstalling the SAMMS-MV Device Full voltage non-reversing connection diagram Grounding the Device SAMMS-MV device communications connections Using the Reset/Test Push Button Password ProtectionPerforming a Lamp Test Performing an Overload Relay TestInput Devices Output DevicesCustom Ladder Diagrams Ladder Diagrams Library of Standard Ladder DiagramsSAMMS-MVX Standard control circuits PB1 PB2 PB3 PB4 PB5 PB6 Motor Ambient Temperature Ridethrough Upon Loss of Power SAMMS-MVX OnlyIncomplete Sequence Intelligent Reduced-Voltage Starting SAMMS-MVX OnlyODP motor thermal signature Protection Curves and Overload Classes Seconds Operating the SAMMS-MV 11 Motor protection graph Phase Unbalance Ultimate Trip Level and Service FactorDual Overload Protection SAMMS-MVX Only Jam Protection SAMMS-MVX OnlyRepetitive Starts Ground Fault DetectionStart Inhibit Cooling Time Constants12 Multi-start scenario for an ODP motor Using the Hand Held Communicator HHC Autoreset After a Trip SAMMS-MVX OnlyEmergency Restarting Function KeyFunction Number 5A CT primary current low speed if used Service factor5A CT primary current if used Full load current for OLR No Motor type Overload trip class class 2 throughUsing the Enter Key Using the SAMMS-MV Device Func- tionsUP and Down Keys ON/OFF Default Value Select ground fault pick-up currentMeans warning Select jam pickup current 120-400% Iflc F24 Loss of Load13 Entering and changing passwords F0 Ambient Temperature Program Mode/PasswordsSAMMS-MV Functions F1 Control Circuit Number and Incomplete Se- quence StatusF3 Size for Overload Relay #2 SAMMS-MVX Only Overload Setting Step Default Relay Size RangeF4 Full-Load Current for Overload Relay #1 18 to 72AF6A Motor Type F6 Service FactorF7 Overload Trip Class F7A Cold Stall TimeF9 Phase Unbalance Protection F8 Autoreset SAMMS-MVX OnlyF10 Display Time to Restart F11 Emergency RestartingF12A Ground Fault Pickup Current F12 Ground Fault Protection or WarningSize Pickup Current Default H3A-H3C 7A-I FLC 10A 20A F13 Set Programmable Timer #1F16 Trip Current F21 Reset Motor DataF17 Current Unbalance F18 Display Total Elapsed Run Time of the MotorF22 Process Current Warning Level SAMMS-MVX Only F25 Percentage of Motor Winding TemperatureF23 Jam Protection SAMMS-MVX Only F23A Jam Pickup Current SAMMS-MVX OnlyF27 Address F26 Baud RateTroubleshooting Error Condition Troubleshooting Guide Error Condition Appendix a Technical Specifications Over load Spec ificat ions Stat ist ica l Data Dimensions Catalog Number SAM6 Switch # Function Position 375 Siemens Energy Automation, Inc