Diagnosis – Check that UF/S and LF/S open, WCR
11)Shutdown (bin full) – Ice fills storage bin to level of BC. BC opens within 10 seconds after ice contact. BCH remains energized. WCR, TDR, GM, FM, CR, and Comp de‑energize.
Diagnosis: When the icemaker is running, hold ice in contact with BC bulb. If the components fail to de‑energize within 10 seconds, check BC. See "IV.C. Bin Control Check."
Legend:
Float Switch
Assembly
Reservoir
Cover
Reservoir
Evaporator
Assembly
Fig. 4
C. Bin Control Check
Drain Plug
Drain Clamp
Drain Hose
Upper Rear Panel
1)Move the power switch to the "ON" position to start the automatic icemaking process.
2)To confirm BC operation, hold ice in contact with BC bulb. If the icemaker does not shut down within 10 seconds, BC must be adjusted. For BC thermostat location, see Fig. 1. Installations at higher altitude locations are more likely to require adjustment. If BC will not shut down the unit even after being adjusted, replace BC. NOTICE! Some units contain a sticker that states: "The bin control heater has been disconnected. DO NOT reconnect the bin control heater." In this case, leave BCH disconnected or replace BC assembly with 3A2561A03.