Monessen Hearth BWBC400I, BWB400I manual Chimney Offset Installation

Page 17
ALL FOUR SUPPORT STRAPS MUST BE NAILED TO FRAMING MEMBER AROUND THE ELBOW WITH A MINIMUM OF TWO (2)
8-PENNY NAILS PER STRAP.

CHIMNEY OFFSET INSTALLATION

ELBOW INSTALLATION

The following are important points that should be observed when installing elbows on the fireplace:

1.The support straps of all elbows not installed directly on top of the fireplace should be nailed securely to the surrounding structure. This allows the support strap to carry the weight of the chimney above the elbow and prevents this weight from breaking the elbow or chimney sections apart. Figure 18.

2.Elbows should not be used in any combination that inclines the chimney more than 30 degrees from

vertical.

FIGURE 18

THE SUPPORT STRAPS OF ALL

ELBOWS NOT INSTALLED DIRECTLY

ON TOP OF THE FIREPLACE SHOULD

BE NAILED SECURELY TO THE

SURROUNDING STRUCTURE.

INLET AIR PIPE

30∞ELBOW

FLUE PIPE

 

3.The limitations on the quantity of elbows per chimney are as follows: If the total height of the fireplace and chimney is — 13' 6" or more — two elbows may be used in the chimney. 21' 0" or more — four elbows may be used in the chimney.

4.The inclined portions of chimneys that pass through living spaces likely to be used for storage should be enclosed to avoid contact with and possible damage to the chimney. The minimum air space of two inches between the chimney and enclosing materials must be maintained. Figures 20 and 21 illustrates elbow installations.

5.The length of the inclined portion of chimney between elbows must not exceed 6 feet when unsupported or 20 feet if the chimney is supported at six-foot intervals with support such as metal support straps.

6.When enclosing the elbows and inclined portions of the chimney, enclosing materials must be installed vertically to maintain the required two-inch minimum air space clearance to the chimney at the extremities of the offset. It is recommended that enclosing material not follow the inclined portions of the chimney.

OFFSET INSTALLATION SEQUENCE

1.Determine the location and amount of offset required, then select the combinations of chimney sections and elbows required from the offset chart. Refer to Table 2.

2.Install the first SE30 elbow by placing the extended flue into the mating part of the fireplace or chimney section. Push down until the outside or inlet air duct of the elbow overlaps and the snaps lock the elbow into the fireplace or chimney section.

3.Nail the support straps to the framing member with a minimum of two 8-penny nails per strap.

4.Install the sections of pipe between elbows until the proper number of chimney sections have been installed.

5.Install the second elbow to return the run of the chimney to vertical.

6.Nail the support straps of the second elbow to a building frame member.

7.Continue installing the vertical portion of the chimney.

NOTE: If the inclined portion of the chimney passes through a floor or ceiling, an SF30 firestop spacer should be installed to provide the firestop and support required. Be sure proper spacing in maintained between the chimney and combustibles. Figure 19.

17

53D9031. Rev 1 03/03

Image 17
Contents Series BWB400-SERIESTable of Contents Important Information Operation Guidelines Clearances Residential InstallationOutside AIR Connector Centerline Fireplace Location Installation Preparation Single Story Installation with Attic Space Floor Protection Fireplace MIN Floor Line with Raised Hearth Fireplace Components See for Illustration of Fireplace Components Described below Fireplace Installation Chimney Installation 17 x Chimney Offset Installation SF30 Firestop Spacer Chimney Offset and CAP InstallationChimney CAP Installation Intermediate Height Sections Inches Chimney Height and Offset ChartsChimney CAP Chase Installation Outside Combustion AIR Precautions and Recommendations Basement Installation Outside Combustion AIR Precautions & RecommendationsGAS Appliance Installation Combustion AIR AssemblyGAS Appliance Installation From Opening Trim InstallationPart a Glass Door Installation and FAN Accessory Fireplace Operation Species Density Heat Value Maintenance and Safety DO’S DONT’S Model Fireplace Parts Diagram and ListBWBC400/BWBC400I Except Blowers Limited WarrantyYour Duties This page intentionally left blank 53D9031. Rev 1 03/03 Appliance Installer BWB500, BWB500I, BWBC500 Congratulations Intended Product Usage Operation Guidelines Residential Installation Framing Corner Installation Side Wall Installation Joist Insulate Same Single Story Installation with Attic Space Brick or Stone Hearth Floor Line with Raised Hearth Fireplace Metal Safety Strip SCS Model Description Fireplace Installation Chimney Installation 17 x Although Both Halves 14-1/2 Chimney CAP Installation Straight RUN Chimney Sections Intermediate Height Inches Chimney CAP Chase Installation Outside Combustion AIR Precautions & Recommendations Outside Combustion AIR Recommendations Model AK4 Combustion AIR Assembly GAS Appliance Installation Applying Decorative Trim to the Fireplace Outline Fireplace Firebrick FAN Assembly Fireplace Operation Species Density Heat Value Maintenance and Safety DO’S DONT’S Model Fireplace Repair Part Diagrams and ListsBWBC500 / BWBC500I FACTORY-BUILT Fireplace and Components Your Duties This page Intentionally Left Blank 53D9032. Rev 1 03/03 53D9032. REV 1 03/03